Plan Review Notes
Plan Review Notes For Permit 03031930
Permit Number 03031930
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-05 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL/LOADS. PANEL A IS SHOWN AS
 A MLO AND PANEL IS LISTED AS MCB ON LOAD
 CALCS.
  
 2)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH CIRCUUIT(S) PER 210-52D/210-11C-3
 SHOWN AS #14/15A.MUST BE 20A #12
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE.
 210-12
  
 4)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 AN EQUIPMENT GROUNDING CONDUCTOR FROM
 METER TO MAIN DISC. PLEASE REMOVE, ONLY
 INSTALLED AFTER FIRST MEANS OF DISC.
 250-24
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected].
  
 PLEASE INSERT NEW SHEETS, TO MAKE TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.