| Plan Review Notes For Permit 03031930 |
| Permit Number |
03031930 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-05 00:00:00 | ************* UNSAT ****************** | | | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM | | | AND PANEL/LOADS. PANEL A IS SHOWN AS | | | A MLO AND PANEL IS LISTED AS MCB ON LOAD | | | CALCS. | | | | | | 2)NOTE: PLEASE LIST THE REQ`D DEDICATED | | | BATH CIRCUUIT(S) PER 210-52D/210-11C-3 | | | SHOWN AS #14/15A.MUST BE 20A #12 | | | | | | 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUITS ON PANEL SCHEDULE. | | | 210-12 | | | | | | 4)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS | | | AN EQUIPMENT GROUNDING CONDUCTOR FROM | | | METER TO MAIN DISC. PLEASE REMOVE, ONLY | | | INSTALLED AFTER FIRST MEANS OF DISC. | | | 250-24 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected]. | | | | | | PLEASE INSERT NEW SHEETS, TO MAKE TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. |
|