| Plan Review Notes For Permit 03031898 |
| Permit Number |
03031898 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-04-29 00:00:00 | ************* PROVISO/NOTES ************ | | | | | | PLEASE SEE NOTES FROM PREVIOUS REVIEWS. | | | | | | 1)NOTE: PLEASE CIRCUIT PLANS AND REVISE | | | SHEETS BEFORE FINAL. | | | PLANS MUST BE REVISED/SIGNED, DATED AND | | | SEALED BY THE ARCH OF RECORD. FS481 | | | PLEASE CORRELATE WITH SUBMITTED PANEL | | | SCHEDULE AND REVISE LOAD CALCAULTIONS TO | | | SHOW ALL CONTINUOUS LOADS AT 125%, | | | 215-5/215-3/230-42 ETC. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|