| Date |
Text |
| 2003-04-10 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 03031898 |
| | ADD: 1601 BELVEDERE RD400/402 |
| | CONT: INTEGRAL CONSTRUCTION |
| | TEL: (954)485-1110 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1)11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | PLEASE REVIEW OFFICE # 4 & 9 ENTRY |
| | DOORS, FOR THE REQUIRED 18" ON THE PULL |
| | SIDE OF THE DOOR. |
| | |
| | OFFICE # 9 IS"AS IS" SEE 20% DISPROP |
| | ORTIONATE COST. THIS IS THE ONLY "AS IS" |
| | ITEM SHOWN ON THE PLAN, THERE IS A POR- |
| | TION OF VTHIS FLOOR NOT INDICATED ON THE |
| | PLAN THAT MAY STILL REQUIRE ADDITIONAL |
| | INFORMATION, OR INSPECTOR MAY SEE IN THE |
| | FIELD AFTER THE PERMIT IS ISSUED! |
| | |
| | 2) PLEASE PROVIDE INFORMATION FOR ENTRY |
| | DOORS TABLE 705.1.2 TENANT SEPERATION |
| | 1 HR./ OPENING PROTECTIVE 45 MIN. (BUILD |
| | INGS NOT SPRINKLERED) |
| | |
| | 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)659-8096 X 8412 |
| | FAX: (561)659-8026 |