Plan Review Notes
Plan Review Notes For Permit 03031892
Permit Number 03031892
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-01 00:00:00THE SBCCI REPORT 9808 FOR THE SHUTTERS
 AND 9606B FOR THE GARAGE DOORS ARE
 EXPIRED.PLEASE PROVIDE CURRENT
 REPORTS.
  
 ARCHITECT, PLEASE PROVIDE AN INDEX OF
 PAGES THAT ARE TO BE USED FOR THE DESIGN
 OF THIS HOUSE.
  
 PLEASE PROVIDE THE ROOF INFORMATION,
 INCLUDING DESIGN PRESSURES AND ROOF
 COVERING ATTACHMENT IN ACCORDANCE WITH
 FBC 104.2.1.1.
  
 SHEET 1 OF THE JUDITH KELLY FOUNDATION
 PLAN CALLS FOR EIGHT INCH THICK ROYALL
 WALL PANELS IN A PORTION OF THE
 BUILDING WHICH IS NOT REFLECTED IN THE
 ROYALL WALL BUILDING SYSTEMS PLANS.
  
 SHOW THE DESIGN PRESSURE FOR THE
 COMPONENTS AND CLADDING AT THE WINDOW
 AND DOOR OPENINGS.THE TABLE ON SHEET
 4 OF THE AFFINITI ARCHITECTURE IS NOT
 SUFFICIENT.SEE FBC 1606.1.7.
  
 PLEASE NOTE THE GLAZING TO BE USED IN
 THE WINDOWS IE; DOUBLE STRENGTH, 3/16,
 HEAT STRENGTHED, ETC.SEE FBC 104.2.
  
 THE US TRUSS ENGINEERING
 DOES NOT SHOW THE MINIMUM 10# LIVE LOAD
 REQUIRED FOR ATTICS IN DWELLINGS
 WITHOUT STORAGE, SEE FBC TABLE 1604.1.
  
 SHOW A CONSTRUCTION DETAIL FOR THE HAND
 AND GUARD RAILS, INCLUDING DESIGN LOADS.
 SEE FBC 1007.5, 1015 AND 1608.2.
  
 PLEASE PROVIDE A CONSTRUCTION DETAIL FOR
 THE INTERIOR BEARING PARTITIONS SHOWN
 ON SHEET 2 OF THE AFFINITI PLANS.SEE
 FBC 104.2.