| Plan Review Notes For Permit 03031885 |
| Permit Number |
03031885 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-16 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS WITH UPDATED SBCCI PRODUCT | | | APPROVAL THAT MATCHES ENGINEERING | | | DRAWINGS. ALSO, CHECK DESIGN PRESSURES | | | AND MAX./MIN. PANEL SPAN. SECTION | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | 2-PROVIDE COMPLETE SPECIFICATIONS FOR | | | GARAGE DOOR STRUCTURAL BUCK DETAIL. | | | NEED ANCHOR EMBEDMENT AND WASHER. SEC. | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | 3-BUILDING SECTION A/A-5: REVISE THE | | | HANDRAIL HEIGHT. SEE SEC. 1007.5.1 | | | FBC 2001. | | | 4-PROVIDE SOIL TEST REPORT PRIOR TO | | | CONSTRUCTION. |
|