| 2003-04-22 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 03031868 |
| | ADD: 2934 S OLIVE |
| | CONT: FRANKLIN CONSTRUCTION |
| | TEL: (561)793-5098 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) SHEET A-5 TWO STORY WALL SECTION; |
| | STUCCO, 1403.1.6 IN ORDER TO PROVIDE FOR |
| | INSPECTION FOR TERMITE INFESTATION, |
| | CLEARENCE BETWEEN EXTERIOR WALL COVER- |
| | INGS AND FINAL EARTH GRADE ON THE EXTER- |
| | IOR OF THE BUILDING SHALL NOT BE LESS |
| | THAN 6 INCHES. |
| | 2304.5 CLEARENCE BETWEEN WOOD SIDING |
| | & EARTH ON THE EXTERIOR OF A BUILDING |
| | SHALL NOT BE LESS THAN 6" EXCEPT WHERE |
| | SIDING, SHEATHING AND FRAME WALL ARE OF |
| | APPROVED DURABLE WOOD OR APPROVED PRE- |
| | SERVATIVE TREAATED WOOD. |
| | |
| | 3) 1707.3.1 JOIST HANGERS, FRAMING |
| | ANCHORS & SIMILAR DEVICES SHALL BE TEST- |
| | ED IN ACCORDANCE W/ ASTM D 1761 & BE |
| | LABELED AND LISTED FOR THEIR LOAD CARRY- |
| | ING CAPACITY. |
| | SHEET A-5 TWO STORY DETAIL, MISSING |
| | THE MANUFACTURER AND LISTED LOAD CARRY- |
| | ING CAPACITY FOR : |
| | A) 1/2" EXP ANCHORS? IS THERE A DERAT- |
| | ING REQUIRED, EDGE DISTANCE? |
| | B) SP6 |
| | |
| | 4) SAME SHEET A-5 DETAIL # 4, INDICATES |
| | THE USE OF A HUGHES ANCHOR, THEY WERE |
| | BOUGHT OUT IN 1999, SEE CURRENT 2003 USP |
| | CATOLOG FOR REFRENCE NUMBER |
| | |
| | 5) SHEET A-5 2 STORY DETAIL, MISSING |
| | CONNECTION OF GAMBERAL ROOF SYSTEM TO |
| | THE SECOND STORY BEARING WALL, AND THE |
| | CONNECTION TO THE FLOOR TRUSS SYSTEM? |
| | THE GIRDER TRUSS HAS NO DETAIL AS TO |
| | HOW THE UPLIFT LOADS ARE BEING TRANSFER- |
| | ED INTO THE EXISTING STRUCTURE, NOR AT |
| | THE NEW END OF THE BUILDING. WILL THERE |
| | BE A POST FOR CONCENTRATED LOADING? |
| | NO MENTION OF A LEDGER NOR BUCKETS IS |
| | INDICATED AS TO THE CONNECTION OF THE |
| | FLOOR TRUSSSES TO THE EXISTING STRUCTURE |
| | |
| | 6) SHEET A-6 FIRST FLOOR PLAN INDICATES |
| | THE USE OF A DOOR # (1) IS THERE A STOOP |
| | ON THE EXTERIOR OF THE DOOR? WHAT WILL |
| | THE DROP FROM FINISH FLOOR BE? |
| | |
| | 7) SHEET A-5 TWO STORY SECTION, MISSING |
| | MOISTURE BARRIER, 1403.3.7.ADHERED |
| | VENEER OVER WOOD FRAME SHALL BE BACKED |
| | BY SOLID SHEATHING COVERED WITH WATER- |
| | PROOF BUILDING PAPER EXCEPT WHERE THE |
| | SHEATHING IS WATER REPELLENT. |
| | |
| | 8) THE PLANS DO NOT INDICATE THE THICK- |
| | NESS OF THE STUCCO, FOR USE ON WOOD |
| | FRAME W/ PAPER BACKED METAL LATH, |
| | 2504.1.3 APPLICATION FOR PORTLAND |
| | CEMENT PLASTER ASTM C 926, FOR A 3 COAT |
| | STUCCO APPLICATION 1ST COAT 1/2", THE |
| | 2ND COAT 1/4" THIRD COAT 1/8"= 7/8" |
| | TOTAL. |
| | |
| | 9) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED.MISSING REPORTS: |
| | A) LOUVERED VENT |
| | B) ROOFING ASSEMBLIES. |
| | C) STORM SHUTTER SCHEDULE SEE SAMPLE |
| | |
| | PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. SEE SAMPLE. |
| | |
| | 10) 2313.4 GABLE ENDWALLS, CATHEDRAL |
| | CEILINGS.FULL HEIGHT STUDS MAY BE SIZED |
| | USING THE BRACING AT A CEILING DIAPHRAM |
| | FOR DETERMINING STUD LENGTH REQUIREMENTS |
| | INDICATE THE END WALL FRAMING! |
| | |
| | 11)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | REMEMBER TO TAKE A CREDIT IF ONE IS |
| | AVAILABLE FOR THE DEMOLITION OF THE |
| | SCREEN PORCH? |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)659-8096 X 8412 |
| | FAX: (561)659-8026 |