 BUILDING PLAN REVIEW
 PERMIT: 03031868
 ADD: 2934 S OLIVE
 CONT: FRANKLIN CONSTRUCTION
 TEL: (561)793-5098
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SHEET A-5 TWO STORY WALL SECTION;
 STUCCO, 1403.1.6 IN ORDER TO PROVIDE FOR
 INSPECTION FOR TERMITE INFESTATION,
 CLEARENCE BETWEEN EXTERIOR WALL COVER-
 INGS AND FINAL EARTH GRADE ON THE EXTER-
 IOR OF THE BUILDING SHALL NOT BE LESS
 THAN 6 INCHES.
 2304.5 CLEARENCE BETWEEN WOOD SIDING
 & EARTH ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6" EXCEPT WHERE
 SIDING, SHEATHING AND FRAME WALL ARE OF
 APPROVED DURABLE WOOD OR APPROVED PRE-
 SERVATIVE TREAATED WOOD.
  
 3) 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
 SHEET A-5 TWO STORY DETAIL, MISSING
 THE MANUFACTURER AND LISTED LOAD CARRY-
 ING CAPACITY FOR :
 A) 1/2" EXP ANCHORS? IS THERE A DERAT-
 ING REQUIRED, EDGE DISTANCE?
 B) SP6
  
 4) SAME SHEET A-5 DETAIL # 4, INDICATES
 THE USE OF A HUGHES ANCHOR, THEY WERE
 BOUGHT OUT IN 1999, SEE CURRENT 2003 USP
 CATOLOG FOR REFRENCE NUMBER
  
 5) SHEET A-5 2 STORY DETAIL, MISSING
 CONNECTION OF GAMBERAL ROOF SYSTEM TO
 THE SECOND STORY BEARING WALL, AND THE
 CONNECTION TO THE FLOOR TRUSS SYSTEM?
 THE GIRDER TRUSS HAS NO DETAIL AS TO
 HOW THE UPLIFT LOADS ARE BEING TRANSFER-
 ED INTO THE EXISTING STRUCTURE, NOR AT
 THE NEW END OF THE BUILDING. WILL THERE
 BE A POST FOR CONCENTRATED LOADING?
 NO MENTION OF A LEDGER NOR BUCKETS IS
 INDICATED AS TO THE CONNECTION OF THE
 FLOOR TRUSSSES TO THE EXISTING STRUCTURE
  
 6) SHEET A-6 FIRST FLOOR PLAN INDICATES
 THE USE OF A DOOR # (1) IS THERE A STOOP
 ON THE EXTERIOR OF THE DOOR? WHAT WILL
 THE DROP FROM FINISH FLOOR BE?
  
 7) SHEET A-5 TWO STORY SECTION, MISSING
 MOISTURE BARRIER, 1403.3.7.ADHERED
 VENEER OVER WOOD FRAME SHALL BE BACKED
 BY SOLID SHEATHING COVERED WITH WATER-
 PROOF BUILDING PAPER EXCEPT WHERE THE
 SHEATHING IS WATER REPELLENT.
  
 8) THE PLANS DO NOT INDICATE THE THICK-
 NESS OF THE STUCCO, FOR USE ON WOOD
 FRAME W/ PAPER BACKED METAL LATH,
 2504.1.3 APPLICATION FOR PORTLAND
 CEMENT PLASTER ASTM C 926, FOR A 3 COAT
 STUCCO APPLICATION 1ST COAT 1/2", THE
 2ND COAT 1/4" THIRD COAT 1/8"= 7/8"
 TOTAL.
  
 9) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) LOUVERED VENT
 B) ROOFING ASSEMBLIES.
 C) STORM SHUTTER SCHEDULE SEE SAMPLE
  
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE. SEE SAMPLE.
  
 10) 2313.4 GABLE ENDWALLS, CATHEDRAL
 CEILINGS.FULL HEIGHT STUDS MAY BE SIZED
 USING THE BRACING AT A CEILING DIAPHRAM
 FOR DETERMINING STUD LENGTH REQUIREMENTS
 INDICATE THE END WALL FRAMING!
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 REMEMBER TO TAKE A CREDIT IF ONE IS
 AVAILABLE FOR THE DEMOLITION OF THE
 SCREEN PORCH?
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026