| Plan Review Notes For Permit 03031863 |
| Permit Number |
03031863 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-03 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BRKRS MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT. 110-9/215-5 | | | | | | 2)NOTE: PLEASE SEE PLAN FOR MISSING | | | HALL RECEPT PER 210-52H/210-52 | | | | | | 3)NOTE: PLEASE SEE 424-3B FOR SIZING | | | OF OCP FOR AHU, SHOWN AS 50A ON 10KW. | | | MIN @125%. | | | | | | 4)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | | CONDUCTOR PER 250-66. MIN FOR 2/0`S IS | | | #4.. | | | | | | 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUITS ON PANEL SCHEDULE PER | | | 210-12 | | | | | | 6)NOTE: PLEASE SEE FS/FAC 61G15-23.002 | | | ALL SHEETS MUST CONTAIN A TITLE BLOCK | | | W/ ALL INFORMATION AS SET FORTH UNDER | | | FS. NAME/ADDRESS/LIC # AND COMPANY | | | IFSO. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] | | | [email protected] |
|