2003-04-03 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SHOWING GROUNDING ELEC-
 -TRODE SYSTEM TO FOOTER STEEL AND COLD
 WATER PIPE. PER 250-50
  
 2)NOTE: PANEL IS NOT PERMITTED ON
 SECOND FLOOR AS SHOWN. PLEASE SEE NEC
 ART 225-32 AND ALSO PER LOCAL AMENDMENTS
 230-70, NO MORE THAN 8' OF UNPROTECTED
 CONDUCTOR ARE PERMITTED INSIDE BLDG.
 PLEASE ADJUST LOCATION OF PANEL.
 PLEASE ALSO CLARIFY TYPE OF LV PANEL
 SHOWN BEHIND DOOR? ALARM? RECEPT REQ`D.
  
 3)NOTE: PLEASE SUBMIT AIC RATING FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 PANELS/MAINS/BREAKERS ALL MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT.110-9/
 215-5
  
 4)NOTE: PLEASE SHOW MIN KW RATING FOR
 WASHER PER 220-16. 1.5KW.
  
 5)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED. PER 210-8-A-6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  