| Plan Review Notes For Permit 03031795 |
| Permit Number |
03031795 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-03 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SHOWING GROUNDING ELEC- | | | -TRODE SYSTEM TO FOOTER STEEL AND COLD | | | WATER PIPE. PER 250-50 | | | | | | 2)NOTE: PANEL IS NOT PERMITTED ON | | | SECOND FLOOR AS SHOWN. PLEASE SEE NEC | | | ART 225-32 AND ALSO PER LOCAL AMENDMENTS | | | 230-70, NO MORE THAN 8' OF UNPROTECTED | | | CONDUCTOR ARE PERMITTED INSIDE BLDG. | | | PLEASE ADJUST LOCATION OF PANEL. | | | PLEASE ALSO CLARIFY TYPE OF LV PANEL | | | SHOWN BEHIND DOOR? ALARM? RECEPT REQ`D. | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATING FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | PANELS/MAINS/BREAKERS ALL MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT.110-9/ | | | 215-5 | | | | | | 4)NOTE: PLEASE SHOW MIN KW RATING FOR | | | WASHER PER 220-16. 1.5KW. | | | | | | 5)NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI | | | PROTECTED. PER 210-8-A-6 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|