Plan Review Notes
Plan Review Notes For Permit 03031795
Permit Number 03031795
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-29 00:00:00THE GARAGE SHOWN ON SHEET A1 DOES NOT
 INDICATE A RIDGE BOARD OR COLLAR BEAMS
 FOR THE ROOF FRAMING.SEE FBC 2309.1.2
 AND 2309.1.7.
  
 PLEASE SHOW A CONSTRUCTION DETAIL FOR
 THE SHED ROOF AND ITS CONNECTION TO THE
 GARAGE.SEE FBC 104.2.
  
 NOTE A SEPARATE PERMIT IS REQUIRED FOR
 THE GARAGE CONSTRUCTION.
  
 PLEASE PROVIDE A CONSTRUCTION DETAIL FOR
 THE FIRE PLACE CHIMNEY.FBC 104.2.
  
 PROVIDE CONSTRUCTION DETAILS FOR THE
 STAIRS.SEE FBC 104.2.
  
 PROVIDE A CONSTRUCTION DETAIL FOR THE
 FRAMED BUMP OUT AT THE STAIRS ON THE
 EAST SIDE.
  
 SHOW A CONNECTION DETAIL FOR THE DORMER
 TO THE TRUSSES.
  
 PLEASE PROVIDE A CALCULATION FOR THE
 ATTIC VENTILATION IN ACCORDANCE WITH
 FBC2309.7.1, INCLUDE THE FREE AREA OF
 THE SCREENED VENTS.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPTATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.