| 2003-09-26 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03031778 |
| | ADD: 610 CLEMATIS STREET |
| | CONT: WHITING- TURNER CONTRACTING |
| | TEL: (954)776-0800 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ARCH B & A BERMELLO AJAMIL & |
| | PARTNERS |
| | BORAS GRANDASEN (305) 860-3822 |
| | HECTOR VALVERDE (305) 859-2050 |
| | |
| | ENG:DER DE LOS ENGINEREERING INC |
| | (305) 665-2778 |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | 2) THRESHOLD BUILDING FL. S.S.553.71(7) |
| | THRESHOLD COMPANY AND INSPECTOR TO BE |
| | SIGNED ON WITH CITY BEFORE ISSUANCE. |
| | CONTACT: DON NEELY 805-6665 |
| | 3) SHEETS A-3.1AB/ A-3.1BC THE ENTERIOR |
| | DOORS TO UNITS ARE TO BE THE "PRIMARY |
| | ENTRY DOORS" FAIR HOUSING ACT INDICATE |
| | MAIN ENTRY ON PLAN NOT SECONDARY. |
| | 4) POOL DECK SHEET A-2.06 THERE IS ONLY |
| | ONE ELEVATION GIVEN, FOR THE WALKING SUR |
| | FACES, PROVIDE SLOPE FOR RAMPS AND ELE- |
| | VATIONS, TO SEE IF HANDRAILS ARE RE- |
| | QUIRED. |
| | 5) SHEET A-3-5DA CORRIDOR 154 LEVEL 42 |
| | (NORTH) INDICATES THE USAGE OF RAMPS, |
| | BUT NO ELEVATION IS PROVIDED NOR SLOPE |
| | FOR THE RAMPS? |
| | 6)1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | A) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST. |
| | SHEET S-1.4.1- S-1.4.3 INDICATE |
| | THE OPENING PRESSURES FOR THE VARIOUS |
| | WALL OPENINGS. THE ONLY PROBLEM IS NO |
| | END ZONES ARE GIVEN FOR THE WALL, CREAT- |
| | ING A HIGHER PRESSURE ZONE,ALSO AT THE |
| | ROOF OR TOP FLOORS. UNDER ASCE7-88 THE P |
| | RESSURES FOR A 80' BUILDING AT ZONE@ 7 |
| | END ZONE 110.3, EVALUATE ROOF LOADS AT |
| | ROOF LEVEL. WHY SUCH A DIFFERENCE? |
| | 7) THE PRODUCT APPROVALS MIAMI-DADE |
| | ARE MISSING THE TECHNICAL SHEETS. THESE |
| | SHEETS INDICATE WHAT THE PRESSURES ARE |
| | APPROVED FOR, ALSO IF REINFORCEMENT |
| | IS REQUIRED. |
| | 8) FENESTRATION TESTING REPORTS RE- |
| | QUIRE SITE SPECIFIC ENGINEERING: |
| | SITE SPECIFIC ENGINEERING (PRODUCT |
| | APPROVAL) REQUIRES THE WET SIGNATURE, |
| | DATE AND EMBOSSED SEAL OF THE ENGINEER |
| | CERTIFYING THE PRODUCT AND SIGNATURE |
| | AND SEAL OF THE DESIGN PROFESSIONAL |
| | OF RECORD.SEE ATTACHMENT. |
| | 9) DEPENDING ON THE REPORT A SEPARATE |
| | MULLION REPORT MAY BE REQUIRED. |
| | 1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | 10) 1707.4.4.2 TAPERED BUCKS: |
| | SHALL EXTEND BEYOND THE INTERIOR FACE |
| | OF THE WINDOW OR DOOR FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS SUPPORTED. |
| | 11) SHEET A-1 GENERAL NOTES: 34, MINI |
| | MUM FLAME SPREAD TO BE IN CONFORMANCE |
| | WITH, ID-11.1 INTERIOR FINISHES, NO IN- |
| | FORMATION ABOUT TABLE 803.3 FLAME SPREAD |
| | / SMOKE DEVELOPMENT.ANSWER COMPLIANCE |
| | BUT WHERE? |
| | 12) EXTERIOR WALLS PRESSURE TREATED |
| | FURRING ALLOWED IF THE FOLLOWING REQUIRE |
| | MENTS ARE MET, 803.9.1. ANSWER SEE NOT |
| | A8.03 NO MENTION OF 803.9.1!!!! |
| | 13) GYMNASIUM A-2 ASSEMBLY INDICATE |
| | 2HR WALLS W/ 1 1/2 HR PROTECTIVE. |
| | ANSWER COMPLIANCE, WHERE? |
| | 14) SHEET A-10.02 DETAILS 1&6 EXPAND- |
| | ED POLYSTRYRENE MOLDING, THIS MATERIAL I |
| | S NOT ALLOWED IN THE FIRE DISTRICT SEE |
| | 102.7 ARCHITECTURAL TRIM. ANSWER: SEE AT |
| | TACHED PRODUCT CONTROL APPROVAL.??????? |
| | 15) SEE DOOR G-37 PART OF EGRESS, |
| | STAIR TOWER# 1, SHOULD SWING OUT. |
| | 16)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |