| 2003-11-13 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | CITY WPB CODE |
| | |
| | A) THE FOLLOWING COMMENTS FROM THE FIRST |
| | AND SECOND REVIEWS HAVE NOT BEEN ADD- |
| | RESSED OR ANSWERED SUFFICIENTLY. THE |
| | NUMBER OF THE COMMENT FROM THE FIRST |
| | REVIEW WILL BE USED FOR CLAIRITY. |
| | 7) SHT A-401 DETAIL #1 CLEAR FLOOR SPACE |
| | REQUIRED FOR ALL FIXTURES PER FHA DESIGN |
| | MANUAL PAGE 7.43. (ALL UNITS) "THE CLEAR |
| | FLOOR SPACE DIMENSIONS ARE TO BE APPLIED |
| | OR SUPERIMPOSED OVER A PLAN DURING THE |
| | DESIGN PROCESS TO DETERMINE IF SPACE RE- |
| | QUIREMENTS AT TOILETS ARE BEING MET. |
| | 13) PLEASE IDENTIFY ALL WORK/LIVE LOFTS. |
| | TOILET ROOMS SHALL COMPLY WITH 11-4.22. |
| | ALL UNITS SHALL HAVE A DRINKING FOUNTAIN |
| | PER TABLE 403.1. ALSO SEE 410.1. - THE |
| | TYPE OF OWNERSHIP DOES NOT DETERMINE IF |
| | REQUIREMENTS ARE TO BE MET, BUT RATHER |
| | THE OCCUPANCY OF THE UNIT THAT DETERMINE |
| | ACCESSIBILITY AND MINIMUM FACILITIES. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. SOME LENGTH MISSING FROM |
| | RISER DIAGRAM. 104.2.1 |
| | B.SHTS P-2.1 & P-2.2 INDICATE A 2 LB. |
| | SYSTEM, BUT SHT P-5.5 STILL INDICATES A |
| | 7" W/C. PLEASE CLAIRFY. 104.2.1 |
| | 22) SHT P-4.2 SANT. RISER DOES NOT REFL- |
| | LECT THE FLOOR PLAN AND SHOWER IS NOT |
| | VENTED. (H/10). 901.2.1 |
| | 23) SHT P-4.4 FLOOR PLAN TO REFLECT THE |
| | SANT. RISER DIAGRAM AT TUB BATH. 104.2.1 |
| | 33) SHT P-4.18 SANT RISER AND FLOOR PLAN |
| | THE KITCHEN SINK SHALL NOT DRAIN INTO |
| | THE WET VENT FOR THE BATHROOM GROUP. |
| | SECTION 909.1 |
| | ---COMMENTS FROM SECOND REVIEW |
| | THE NUMBERS WILL REMAIN THE SAME FOR |
| | CLAIRITY. |
| | 6B) SHTS P-2.1 & P-5.2 RISERS 27 THRU 41 |
| | AT COL. LINE 8 SHOWS 300 DFU'S ON FLOOR |
| | PLAN, BUT 370 DFU'S ON RISER. PLEASE |
| | CLAIRFY. (RISER 38 NOT SHOWN ON FLOOR |
| | PLAN, BUT IS SHOWN ON THE SANT. RISER |
| | DIAGRAM). 104.2.1 |
| | 9B) SHTS P-2.3 & P-5.5, 8" SHOWS 1298 |
| | DFU ON FLOOR PLAN BUT NOT RISER SHOWS |
| | 1365 DFU. RISER AND FLOOR PLAN SHALL RE- |
| | FLECT. PLEASE CLAIRFY. 104.2.1 |
| | 10B) SHTS P-2.4 & P-5.5 RISER DOES NOT |
| | REFLECT THE FLOOR PLAN. BRANCH TO TOILET |
| | ROOMS CONNECT TO DRAIN AFTER SR128 ON |
| | THE FLOOR PLAN, BUT PRIOR TO SR 128 ON |
| | THE RISER DIAGRAM. PLSE CLAIRFY 104.2.1 |
| | 11B) SHTS P-2.4 & P-5.6 FLOOR PLAN SHOWS |
| | 8" @ 9450 SF, BUT RISER SHOWS 10" @ |
| | 9450 SF. PIPE SIZES MUST CORRELATE. |
| | 15B) SUBMIT STORM RISERS, SHOW OFFSETS, |
| | PIPE SIZES, SQUARE FOOOTAGE ECT. THE |
| | HORIZONTAL STORM DRAIN IS SHOWN BUT THE |
| | VERTICAL STORM RISERS ARE NOT SUBMITTED. |
| | 104.2.1 |
| | 19B) SUBMIT CALCULATIONS FOR RWL'S LARG- |
| | ER THAN 8". TABLE 1106.2 ONLY ADDRESSES |
| | PIPE SIZE TO 8". 104.2.1 - THIS WILL BE |
| | REQUIRED FOR PERMIT. |
| | 25B) SHT P-4.3 TUB NOT VENTED, B/11 AND |
| | ALL AAV'S REQUIRES ACCESS, AND VENTILA- |
| | TION. 917.5 |
| | 26B) SHT P-4.5 TUB NOT VENTED AND RISER |
| | DOES NOT REFLECT THE FLOOR PLAN. UR-1 |
| | HORIZONTAL DRY VENT NOT ALLOWED. 905.3 |
| | THIS VENT IS NOT REQUIRED. UR-3. 104.2.1 |
| | AAV REQUIRES ACCESS AND VENTILATION. |
| | 917.5. "S" TRAP ON LAV (NO VENT) 1002.3 |
| | (5) - SEE RED LINES |
| | 27B) SHT P-4.6 SHOWER NOT VENTED, ACCESS |
| | & VENTILATION REQUIRED FOR AAV, NO HORI- |
| | ZONTAL DRY VENTS NOT ALLOWED. |
| | 28B) SHT P-4.7 ACCESS AND VENTILATION |
| | REQUIRED FOR AAV, RISER DOES NOT REFLECT |
| | THE FLOOR PLAN. |
| | 29B) SHT P-4.9 ACCESS AND VENTILATION |
| | REQUIRED FOR AAV'S. 917.5 |
| | 30B) SHT P-4.10 SHOWER NOT VENTED L-05 |
| | 901.2.1 |
| | 31B) ACCESS AND VENTILATION REQUIRED FOR |
| | AAV'S 917.5 |
| | 32B) SHT P-4.13 TUB NOT VENTED U-1 |
| | 33B) SHT P-4.14 SHOW VENT ON FLOOR PLAN |
| | 104.2.1 |
| | 34B) SHT P-4.15 SHOWER NOT VENTED, AND |
| | VENT NOT REQUIRED ON TUB. |
| | 35B) SHT P-4.17 ACCESS AND VENTILATION |
| | REQUIRED FOR AAV. HORIZONTAL DRY VENT |
| | NOT ALLOWER FOR SHOWER. 905.3 |
| | 36B) THE RELIEF VENTS REQUIRED BY SEC |
| | 917.3.2 FOR FLOORS 2, 3, & R SHALL BE |
| | TIED INTO THE BRANCH LINES FOR THESE |
| | FLOORS. THE VENT LINES SHALL BE SHOWN |
| | ON THE RISERS. SEE EXAMPLE ON SR/20 |
| | |
| | REVIEW BY KEN STEVENS |