| 2003-11-13 00:00:00 | DENIED: |
| | PLEASE NOTE THE FOLLOWING INFORMATION |
| | NOT ANSWERED FROM PREVIOUS REVIEW BY |
| | HAROLD MOSER DATED 9-22-03. |
| | |
| | #1BALANCED AIR RETURN - PLEASE NOTE |
| | PLANS DO NOT INDICATE ANY SIZE FOR THE |
| | TRANSFER OR RETURN AIR GRILLES.PLEASE |
| | SEE THE ATTACHED FOR PROPER SIZING. |
| | INDICATE SIZING ON PLAN. |
| | |
| | #3 & 5 FRESH AIR FROM RTU-1, PLEASE NOTE |
| | THE LOCATION OF THE FRESH AIR SHALL BE |
| | RECIRCULATED INTO THE SYSTEM.PLEASE |
| | EXPLAIN HOW THIS COMPLIES WITH ASHRAE |
| | 62-89 SECTION 6.1.3.2 & 6.1.3.3. |
| | |
| | REVIEW BY PATTY KRAUSS: |
| | CLARIFY THE FOLLOWING INFORMATION: |
| | 1. PLAN SHEET M-2.3 O.A. SHALL HAVE A |
| | 10 FT SEPARATION FROM NOXIOUS EXHAUST AS |
| | PER 2001 FBC(M) 401.5.1. |
| | |
| | 2.PLAN SHEET M-2.6 PLEASE CLARIFY |
| | O.A. LOUVER INTO RETAIL SPACE #4 & 5, |
| | WILL THIS BE USED FOR FUTURE O.A. WILL |
| | IT BE DUCTED? SEE COMMENT #3 ABOVE. |
| | |
| | 3.PLAN SHEET M-2.10 E/A DUCT UP TO REF |
| | 12 WHAT WILL THIS BE FOR TOILET & DRYER |
| | EXHAUST? DETAILS INDICATE TOILET & DRYER |
| | THRU THE UNIT TO AN OUTSIDE WALL (M-4.1) |
| | |
| | 4.PLAN SHEET M-3.1 GENERATOR EXHAUST |
| | SHALL BE A MINIMUM OF 10 FT ABOVE THE |
| | ADJOINING GRADE. |
| | |
| | 5.PLAN SHEET M-4.1 HVAC GENERAL NOTES |
| | FURNISH & INSTALL TRANSFER GRILLES & |
| | RETURN AIR CENTERED ABOVE THE BATHROOM |
| | DOORS.AIR FROM BATHROOM AREA SHALL NOT |
| | BE RECIRCULATED EXHAUST ONLY PER 2001 |
| | FBC(M) TABLE 403.3.PLEASE SEE ATTACHED |
| | FOR PROPER SIZING OF TRANSFER GRILLES |
| | AND RETURN AIR DUCTS. INDICATE DUCT & |
| | GRILLE SIZES AND LOCATIONS ON PLANS. |
| | |
| | 6.PLEASE PROVIDE O.A. CALCULATIONS FOR |
| | THE COMMON AND RESIDENTIAL AREAS AS PER |
| | 2001 FBC(M) TABLE 403.3 & ASHRAE 62-89. |
| | |
| | 7.PLEASE NOTE O.A. & EXHAUST AIR FROM |
| | THE EMERGENCY GENERATOR RM, PUMP RM, |
| | SWITCHGEAR RM & ELEC RM IS ALL TAKEN |
| | FROM THE GARAGE AREA. |
| | |
| | 8.PROVIDE ENERGY CALCULATIONS. |
| | |
| | 9.PROVIDE MANUFACTURER SUBMITTAL DATA |
| | FOR THE EMERGENCY GENERATOR. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561) 805-6719. |