| 2003-11-06 00:00:00 | 1) ELECTRONIC SWITCHES WILL BE |
| | REQUIRED ON THE FIRE-LINE BACKFLOW |
| | DEVICE. |
| | |
| | 2) PLEASE EXPLAIN VARIABLE TREADS ON |
| | GROUND FLOOR PLAZA STEPS HARDSCAPE. |
| | |
| | 3) PROPANE GRILL DETAIL STILL |
| | SHOWN ON L-7.2. |
| | |
| | 4) EXPANDED POLYSTYRENE MOLDING STILL |
| | SHOWN A-102, TYPICAL BALCONY DETAILS. |
| | |
| | 5) DOUBLE DOORS ON GROUND FLOOR |
| | LS PLAN-104 STILL SHOWS THE DOUBLE |
| | DOORS OPENING INWARD. PLEASE VERIFY |
| | DOUBLE DOORS SWING AND CORRECT |
| | ANY DEFICIENCIES. |
| | |
| | 6) TRASH CHUTE DOORS ON PAGE A-2.07 |
| | AND OTHER SHEETS NEAR 303 APPEARS |
| | TO SWING INTO CORRIDOR TOO FAR. |
| | |
| | 7) INFORMATION CONCERNING ROOF PLAN |
| | PAGE A-2.11 IS DIFFICULT TO READ. |
| | |
| | 8) PLEASE EXPLAIN WHY SHAFT ACCESS |
| | OPENING IS LOCATED NEXT TO EXIT DOOR. |
| | PLEASE EXPLAIN RATIONALE. |
| | |
| | 9) STORAGE OPENINGS S26,S27,S41 DOORS |
| | OPPOSE ONE ANOTHER. S36,S37 ALSO |
| | OPPOSE ANOTHER. |
| | |
| | 10) DOORS STILL SWING OVER THE STAIRS |
| | ON PAGE A-4.02. |
| | |
| | 11) FABRIC AWNINGS ARE TO BE FIRE |
| | RETARDANT. |
| | |
| | 12) PORTIONS OF THE BUILDING ARE OVER |
| | THE PROPERTY LINE ON PAGE A-5.02. |
| | |
| | 13) EXPANDED POLYSTYRENE STILL SHOWN |
| | ON WALL SECTION DETAILS. |
| | |
| | 14) WHAT IS THE VOID BELOW THE |
| | ELEVATOR MACHINE ROOM GOING TO BE |
| | USED. |
| | |
| | 15) PLEASE PROVIDE PRESCRIPTIVE |
| | STRENGTH REQUIREMENT FOR HANDRAILS |
| | AND GUARDRAILS. |
| | |
| | 16) FIRE EXTINGUISHER CABINET DISPLAYS |
| | BREAK GLASS BUT NO BREAK GLASS RODS |
| | SHOWN. |
| | |
| | 17) SOME TRASH CHUTE DOORS STILL |
| | APPEAR TO BE TOO LARGE FOR THE |
| | CORRIDORS. |
| | |
| | 18) PLEASE EXPLAIN WHY SHAFT OPENING |
| | IS LOCATED DIRECTLY NEXT TO EXIT DOOR |
| | ON M-1.1. |
| | |
| | 19) PROVIDE SEPARATE PLANS AND PERMITS |
| | FOR GENERATOR AND ASSOCIATED FUEL |
| | TANK. |
| | |
| | 20) EXIT SIGNS APPEAR TO BE MISSING |
| | ON PAGE E-2.4 DIRECTING PERSONS TO |
| | STAIRWELL. |
| | |
| | 21) FIRE COMMAND NOTES ON E-2.5 DOES |
| | NOT APPEAR TO CONTAIN ALL EQUIPMENT. |
| | PLEASE REVIEW FBC SECTION 412.4. |
| | |
| | 22) AN EXIT SIGN APPEARS MISSING FROM |
| | GARAGE AREA NEAR DOUBLE DOORS. |
| | |
| | 23) EXIT SIGNS APPEAR TO BE MISSING |
| | FROM E-2.6 FROM GARAGE AREA. ALSO |
| | NO DIRECTIONAL SIGNS ARE PRESENT TO |
| | DIRECT PERSONS FROM RETAIL # 5. |
| | |
| | 24) MORE EXIT SIGNS APPEAR TO BE |
| | NEEDED ON E-2.7. |
| | |
| | 25) PLEASE EXPLAIN EXIT SIGN FROM |
| | RESTROOMS TO GARAGE AREA. |
| | |
| | 26) ONLY ONE STANDPIPE VALVE SHOWN ON |
| | FP-11. |
| | |
| | 27) FDC FACES THE WRONG DIRECTION. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |