| Plan Review Notes For Permit 03031778 |
| Permit Number |
03031778 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-10-29 00:00:00 | ********* NOTES REDLINED *********** | | | | | | 1)NOTE: GFI RECEPTS TO BE W/IN 3' OF | | | LAV/ SINKS IN BATHROOMS. | | | E-4.11(L-19), E-4.16 (R1(N) | | | | | | 2)NOTE: RECEPT SPACING PER 210.52 | | | E-4.5 (16,18,20), 4.5 (T1), 4.18 (M/01, | | | M38 | | | | | | 3)NOTE: COLOR CODING REDLINED FOR CITY | | | OF WEST PALM BEACH AMEDMENTS. | | | PLANS MENTION PALM BEACH COUNTY. | | | | | | THE ABOVE HAS BEEN REDLINED ON EACH SET | | | AND PLANS DO NOT NEED TO BE REVISED AT | | | THIS TIME FOR THIS. | | | ELECTRICAL PLANS HAVE BEEN PASSED, PEND- | | | -ING COMMENTS FROM ANY OTHER REVIEWERS | | | THAT MAY OR MAY NOT HAVE COMMENTS THAT | | | MAY AFFECT ELECTRICAL PLANS. | | | ELEECTRICAL SHEETS ONLY HAVE BEEN | | | STAMPED. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | PLANS SUBMITTED FOR TEMPORARY ELECTRICAL | | | SERVICE MUST BE SUBMITTED UNDER SEPARATE | | | PERMIT APPLICATION. | | | PLEASE ALSO HAVE PLANS DONE AND AN | | | ENGINEER PER FS 471.003 | | | PLANS MUST CONTAIN ALL INFORMATION AS | | | SET FORTH UNDER FAC 61G15-23.002 |
|