| 2003-04-16 00:00:00 | BUILDING PLAN REVIW |
| | CONTINUED 4/16/03 |
| | |
| | *****STAIR TOWERS****** |
| | 42) SECTION 1005.6.6 APPROVED BARRIERS: |
| | A STAIRWAY IN A SMOKEPROOF ENCLOSURE |
| | SHALL NOT CONTINUE BELOW GRADE LEVEL |
| | UNLESS AN APPROVED BARRIER IS PROVIDED |
| | AT THE GROUND LEVEL TO PREVENT PERSONS |
| | FROM ACIDENTALLY CONTINUING INTO THE |
| | BASEMENT. |
| | 1007.1.5 ENCLOSED EXIT STAIRWAYS |
| | THAT CONTINUE BEYOND THE FLOOR OF DIS- |
| | CHARGE SHALL BE INTERRUPTED AT THE FLOOR |
| | OF DISCHARGE BY PARTITIONS, DOORS OR |
| | OTHER EFFECTIVE MEANS. |
| | STAIR TOWERS 1, 2& 3 HAVE THIS CONDI |
| | TION THAT REQUIRES SOME MEANS TO PREVENT |
| | A PERSON FROM TURNINGIN THE WRONG |
| | DIRECTION AND DECENDING INTO THE |
| | BASEMENTS. |
| | |
| | 43)SECTION 1006.1.3.2 EXTERIOR WALLS OF |
| | AN ENCLOSED STAIRWAY SHALL COMPLY WITH |
| | THE REQUIREMENTS OF TABLE 600 FOR EXTER- |
| | IOR WALLS. WHERE NONRATED WALLS OR |
| | UNPROTECTED OPENINGS ARE USED TO ENCLOSE |
| | THE EXTERIOR OF THE STAIRWAY, THE BUILD |
| | ING ENCLOSURE WALLS WITHIN 10 FT HORIZON |
| | TALLY OF THE NONRATED WALLS OR UNPROTECT |
| | ED OPENINGS SHALL BE CONSTRUCTED AS REQU |
| | IRED FOR STAIRWAY ENCLOSURES, INCLUDING |
| | OPENING PROTECTIVES, BUT NEED NOT EXCEED |
| | 1-HR FIRE RATING W 3/4 HOUR OPENING PROT |
| | ECTIVE. THIS CONSTRUCTION SHALL EXTEND |
| | VERTICALLY FROM THE GROUD TO A POINT |
| | 10 FT ABOVE THE TOP MOST LANDING OF THE |
| | STAIRWAY OR TO THE ROOF LINE, WHICHEVER |
| | IS LOWER. |
| | STAIRWELLS 1,2 & 3 HAVE THIS CONFIG |
| | URATION WHERE THE WINDOWS/ DOORS EITHER |
| | SIDE OF THE OPENING OR ABOVE THE OPENING |
| | ARE NOT RATED. |
| | STAIRWELL # 3 SEE 1005.6.8.1 FOR |
| | SMOKEPROOF ENCLOSURE BY NATURAL VENTIL- |
| | ATION VESTIBULE AS OPTION. |
| | |
| | 43) RETAIL AREAS, 1004.1.2 EVERY ROOM OR |
| | TENANT SPACE WHICH HAS AN OCCUPANT LOAD |
| | OF 50 OR MORE PERSONS SHALL NOT HAVE |
| | LESS THAN 2 EGRESS DOORS, REMOTELY |
| | PLACED. IF THESE SPACES ARE FITTED OUT |
| | AS RESTARAUNTS, THE BACK EXIT IF THROUGH |
| | THE KITHEN CAN'T BE COUNTED AS AN EXIT! |
| | JUST A WORD OF CAUTION! |
| | |
| | 44) 1012.1.2 EGRESS DOORS SHALL SWING IN |
| | THE DIRECTION OF TRAVEL (1) WHEN SERVING |
| | AN OCCUPANT LOAD OF 50 OR MORE, SEE |
| | GYMNASIUN DOOR! PROVIDE ADDITIONAL INFO |
| | FOR THE CARD READER ON THIS DOOR, LOSS |
| | OF POWER FAIL SAFE OPEN OR FAIL SAFE |
| | SECURE? |
| | |
| | 45) ID-9-0 ELEVATORS 3003.4.1 PROVIDE |
| | LAYOUT INDICATING STRETCHER REQUIREMENTS |
| | |
| | 46) ELEVATOR SIGNAGE 3003.3. |
| | |
| | 47)1503.4.2 OVERFLOW DRAINS SHALL BE |
| | THE SAME SIZE AS ROOF DRAINS, INSTALLED |
| | WITH THE INLET FLOW LINE LOCATED 2" |
| | 0BOVE THE LOWEST POINT OF THE ROOF LINE. |
| | OVERFLOW SCUPPERS SHALL BE A MINIMUM OF |
| | 4"IN HEIGTH AND SHALL BE PLACED IN WALLS |
| | OR PARARETS WITH THE INLET FLOW LINE |
| | NOT LESS THAN 2" ABOVE THE ROOF SURFACE. |
| | |
| | SHEET A-10.02 DETAIL # 2/ WHAT IS THE |
| | OVERFLOW SCUPPER SIZE? |
| | |
| | 48) 1503.4.4 PROTECTION AGAINST DECAY & |
| | TERMITES. CONDENSATE LINES & ROOF DOWN |
| | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| | AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| | TENSIONS, OR SPLASH BLOCKS. |
| | |
| | 49) 1511.7 ROOF MOUNTED MECHANICAL UNITS |
| | SHALL BE MOUNTED ON CURBS RAISED A |
| | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| | FACE, OR WHERE ROOFING MATERIALS EXTEND |
| | BENEATH THE UNIT, ON RAISED EQUIPMENT |
| | SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| | HEIGTH IN ACCORDANCE WITH TABLE 1511.7. |
| | |
| | 50) SHEET A-5.14 LOWER PARKING FLOOR, |
| | THE 7'-0" CLEAR FLOOR HEIGHT MUST BE |
| | MAINTAINED, THIS IS A MINIMUM!!!! |
| | |
| | 51) INDICATE WHAT HR RATING THE CONCRETE |
| | BLOCK USED WILL BE, EQUIVALENT THICKNESS |
| | WILL BE FOR THE MANUFACTURER USED? |
| | TABLE 709.3.1. |
| | |
| | 52) SHEET A10.07 FABRIC CANOPY- FABRIC |
| | IS TO BE FIRE RETARDANT TREATED FABRIC. |
| | F102.2.8. |
| | |
| | 53) SHEET A-10.10 TEAHOUSE/ TRILLIS |
| | NO TYPE VI CONSTRUCTION IN THE FIRE |
| | DISTRICT |
| | |
| | 54) ID-2.2 MAIN LOBBY CURVED SOFFITS, |
| | DROPPED CEILING, FIBERGLASS PLASTIC |
| | DOME( ID-4.1 DETAIL 6) ADDITIONAL INFO, |
| | HOW TO HANG, MAN SPEC FLAME SPREAD/ |
| | SMOKE DEVELOPMENT? |
| | |
| | 55) ID-4.2 MAIL KIOSK DETAILS 3&6, REACH |
| | RANGES?11-4.2.5/11-4.2.6 FL ACC CODE. |
| | |
| | 56)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)659-8096 X 8412 |
| | FAX: (561)659-8026 |