| 2005-08-04 00:00:00 | REVISION DENIED/OK |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1. SHT P-1.2 REVISIONS 1, 13, 17 NOT |
| | FOUND ON REVISED SHEET. MANY CHANGES TO |
| | SHEET NOT CLOUDED OR NUMBERED. INDICATE |
| | ALL REVISIONS TO SHEET BY CLOUDING AND |
| | NUMBERING. SECTION 104.2.1. |
| | 2. SHT P-1.3 REVISION 1 DESCRIPTION |
| | UNCLEAR. REVISIONS 11 & 17 NOT FOUND. |
| | MANY CHANGES TO SHEET NOT CLOUDED OR |
| | NUMBERED. INDICATE ALL REVISIONS TO |
| | SHEET BY CLOUDING AND NUMBERING. SECTION |
| | 104.2.1. |
| | 3. SHT P-2.1 NOTE TO CONTRACTOR READS |
| | "GAS PIPING SHALL BE WELDED SCHEDULE 40 |
| | BLACK STEEL". PRIOR TO ISSUING THE |
| | PERMIT & PLANS, THE ENGINEER INDICATED |
| | THAT THE GAS PIPING WILL BE SCREW PIPE |
| | AND NOT WELD PIPE. PLEASE CHANGE THIS ON |
| | THE NOTE. - ORIGINAL ISSUED SET OF PLANS |
| | HAD MEASURMENTS FOR EACH SECTION OF GAS |
| | PIPE HAND DRAWN BY THE ENGINEER. THESE |
| | MEASURMENTS SHALL BE ON THE REVISED |
| | SHEET. SOME CHANGES TO SHEET ARE NOT |
| | CLOUDED OR NUMBERED. INDICATE ALL |
| | REVISIONS TO SHEET BY CLOUDING AND |
| | NUMBERING. SECTION 104.2.1. |
| | 4. SHTS P-2.9 AND P-2.10 REVISION 1 NOT |
| | FOUND, (P-2.9). GIVE A DISCRIPTION OF |
| | WHAT REVISION 20 IS FOR. LINES SHOWN DO |
| | NOT CONNECT TO ANY SYSTEM, NO PIPE SIZES |
| | SHOWN. WHAT IS THE INTENT OF THESE |
| | LINES? SECTION 104.2.1. SECONDARY ROOF |
| | DRAINS ARE NOT SHOWN FOR THIS AREA OF |
| | THE DECK AS REQUIRED IN SECTION 1107. |
| | PLEASE INDICATE THE LOCATION. SECTION |
| | 104.2.1. |
| | 5. SHT P-2.11 INDICATES 4" PATIO |
| | OVERFLOW DRAINS FOR ONE SET OF LINES |
| | ADJACENT TO THE MATCH LINE. IS THIS THE |
| | REQUIREMENT FOR ALL LINES SHOWN ON THIS |
| | SHEET AS REVISION 20? IS THIS THE |
| | REQUIREMENT FOR ALL SHEETS SHOWING THESE |
| | LINES? IF SO PLEASE INDICATE IN SOME WAY |
| | TO CLARIFY THESE COMMENTS. SECTION |
| | 104.2.1. |
| | 6. SHTS P-2.11, P-2.12, THESE AREAS |
| | REQUIRED SECONDARY ROOF DRAINS. PLEASE |
| | SHOW THE LOCATION OF SECONDARY ROOF |
| | DRAINS PER SECTION 1107. |
| | 7. SHT P-4.1 OK |
| | 8. SHT P-4.2 MAXIMUM 8' FROM TRAP TO |
| | VENT PER TABLE 906.1 - SCALES OUT TO |
| | ABOUT 10' ON DETAIL 1. |
| | 9. SHT P-4.3 OK |
| | 10. SHT P-4.4 OK |
| | 11. SHT P-4.5 OK |
| | 12. SHT P-4.6 OK |
| | 13. SHT P-4.7 OK |
| | 14. SHT P-4.8 OK |
| | 15. SHT P-4.9 OK |
| | 16. SHT P-4.10 MAXIMUM 8' FROM TRAP TO |
| | VENT PER TABLE 906.2 - SCALES OUT TO |
| | ABOUT 11' ON DETAIL 1. - CHANGE TO FLOOR |
| | PLAN SHALL BE REFLECTED BY A CHANGE TO |
| | THE SANT. RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 17. SHT P-4.11 OK |
| | 18. SHT P-4.12 OK |
| | 19. SHT P-4.13 REVISION 1 NOT FOUND. |
| | SECTION 104.2.1. |
| | 20. SHT P-4.14 REVISION 1 NOT FOUND. |
| | SECTION 104.2.1. |
| | 21. SHT P-4.15 REVISION 1 NOT FOUND. |
| | SECTION 104.2.1. |
| | 22. SHT P-4.16 MAXIMUM 8' FROM TRAP TO |
| | VENT PER TABLE 906.2. - SCALES OUT TO |
| | ABOUT 11' ON DETAIL 2. |
| | 23. SHT P-4.17 HAND DRAWN CHANGE TO |
| | SHEET DATED 11-19-03 HAVE NOT BEEN |
| | CHANGED AND ARE SHOWN AS DRAWN |
| | ORIGINALLY. THESE WERE CODE COMPLIANCE |
| | CHANGES AND SHALL BE REFLECTED ON THIS |
| | SHEET AS REQUIRED AT TIME PERMIT ISSUED. |
| | NO REVISION SHOWN CHANGING DETAILS 1 AND |
| | 4 AT THE KITCHEN SINK FOR THE LOCATION |
| | OF THE AAV. SECTION 104.2.1. |
| | 24. SHT P-4.18 OK |
| | ALL OK SHEETS DATE STAMPED AND RETURNED |
| | WITH DENIED SHEETS AND WILL NOT BE |
| | REQUIRED TO BE RESUBMITTED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |