| 2003-09-12 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | CITY WPB CODE |
| | |
| | A) FOLLOWING COMMENTS FROM THE FIRST RE- |
| | VIEW HAVE NOT BEEN ADDRESSED OR ANSWERED |
| | SUFFICIENTLY. THE NUMBER OF THE COMMENT |
| | FROM THE FIRST REVIEW WILL BE USED FOR |
| | CLAIRTY. |
| | 7) SHT A-4.01 DETAIL #1 CLEAR FLOOR |
| | SPACE REQUIRED FOR ALL FIXTURES PER FHA- |
| | DESIGN MANUAL PAGE 7.43 (ALL UNITS). |
| | 12) SHT A-2.11 SCUPPER DETAIL, SUBMIT |
| | INFO. FOR SCUPPERS SHOW ALL MEASUREMENTS |
| | & INDICATE SLOPEAT THE BOTTOM OF THE |
| | TRENCH IF ANY. SHOW LONGEST TRENCH MEAS- |
| | UREMENT. SECTION 104.2.1 |
| | 13) PLEASE IDENTIFY ALL WORK/LIVE LOFTS. |
| | TOILET ROOMS SHALL COMPLY WITH 11-4.22. |
| | ALL UNITS SHALL HAVE A DRINKING FOUNTAIN |
| | PER TABLE 403.1. (ALSO SEE 410.1) |
| | 14) SUBMIT WORKSHEET FROM R. COMPO FOR |
| | GREASE INTERCEPTOR. ORD. 2938-96 |
| | 16) SHTS P2.1/P2.2 SEPARATE GAS PERMIT |
| | REQUIRED. THE FOLLOWING INFORMATION IS |
| | REQUIRED PRIOR TO PERMIT ISSUANCE. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. - RISER NOT SUBMITTED IN |
| | ISOMETRIC FORM & ALL CUT SECTIONS OF |
| | PIPE LENGTHS NOT SHOWN. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | - INDICATE IF PIPE WILL BE WELDED OR |
| | SCREW PIPE. IF WILDED PIPE, WELDERS |
| | CERTIFICATE, AND PICTURE I.D. WILL BE |
| | REQUIRED WITH THE WELDING PROCEDURE BE- |
| | FOR STARTING. |
| | PLANS INDICATE 7" W.C.TABLES IN FBC-2001 |
| | FUEL GAS SHOW MINIMUM GAS PRESSURE AT |
| | 14" W.C. PLEASE VERIFY THE DELIVERY |
| | PRESSURE WITH GAS PROVIDER. PROVIDE |
| | TABEL USED FOR SIZING GAS PIPE. SUGGEST |
| | A 2 LB SYSTEM BE USED AS THE PIPE SIZE |
| | IS NOT SUFFICIENT FOR 1/2 LB PRESSURE. |
| | 21) SHT P-4.1 KITCHEN SINK SHALL NOT |
| | DRAIN INTO THE WET VENT OF THE BATHROOM |
| | GROUP. SECTION 909.1. |
| | 22) SHT P-4.2 SANT. RISER DOES NOT RE- |
| | FLECT THE FLOOR PLAN AT TUB & SHOWER. |
| | SHOWER NOT VENTED. SECTION 901.2.1 |
| | 23) SHT P-4.4 SANT. RISER DOES NOT RE- |
| | FLECT THE FLOOR PLAN. TUB NOT VENTED, |
| | SHOWER NOT VENTED. 104.2.1 - 901.2.1 |
| | 31) SHTS FOR ALL UNITS, WATER HAMMER |
| | ARRESTORS REQUIRED AT ICE MAKER LINE. |
| | SECTION 604.9 |
| | 33) SHT P-4.18 SANT. RISER KITCHEN SINK |
| | SHALL NOT DRAIN INTO WET VENT FOR BATH- |
| | ROOM GROUP. SECTION 909.1 |
| | 34) SHT P-5.1 RISER SR4 N/203/19 DFU NOT |
| | ADDED TO TOTAL FOR RISER. |
| | 37) SHT P-5.4 DETAIL #1 RPZ BACKFLOW TO |
| | BE MAX. 4' ABOVE FLOOR FOR SERVICING AND |
| | TESTING. |
| | 40) SHT P-5.5 INDICATES DETAIL FOR |
| | GREASE TRAP ON SHT P-7.1, BUT NO DETAIL |
| | FOUND. PROVIDE DETAIL. |
| | 42) SHT P-5.5 DFU'S FROM GREASE TRAP NOT |
| | ADDED TO SYSTEM. RECALCULATE DFU'S. SHOW |
| | SLOPE OF PIPE ON RISER DIAGRAM. |
| | 49) SHT P-5.6 PLEASE INDICATE MATERIAL |
| | FOR RELIEF VALVE & EMERGENCY PAN DRAIN |
| | RISERS. RESPONSE ON DETAIL #4 CALLS FOR |
| | CAST IRON DRAIN FOR HEATER PANS. PLEASE |
| | NOTE THAT MINIMUM SIZE FOR CAST IRON IS |
| | 2". PLEASE CLAIRFY. |
| | 52) SHT P-7.1 AIR CHAMBER DETAIL. AIR |
| | CHAMBERS ARE NOT APPROVED. PLEASE DELETE |
| | DETAIL. |
| | ********NEW COMMENTS********* |
| | 1B) SHT P-1.2 COL. LINE 2/F NO CHANGE |
| | NOTED. CLO. LINE 2/K REVISION NOT CLOUD- |
| | ED. 104.2.1 |
| | 2B) SHT P-1.2 COL. LINE 11/R.2 SQUARE |
| | FOOTAGE DIFFERENT FROM RISER. PLEASE |
| | CLAIRFY 104.2.1 |
| | 3B) SHT P-1.2 15" STORM (58,220 SF) IN- |
| | DICATE SLOPE OF PIPE FOR HORIZONTAL OFF- |
| | SET. (SHT P1.3 INDICATES 54,570 SF, |
| | RISER SHT P5.6 INDICATES 63,464 SF BUT |
| | ADDS UP TO 64,689 SF. PLEAS CLAIRFY. |
| | PLEASE CHECK ALL SQUARE FOOTAGE FOR |
| | STORM PIPING. FLOOR PLAN AND RISERS FOR |
| | NOT REFLECT.104.2.1 |
| | 4B) SHTS P-1.3 & P-5.5 FLOOR PLAN & SANT |
| | RISER DIAGRAM. LOCKING VALVE FOR FOUNT- |
| | AIN POOL DRAINAGE NOT SHOWN ON FLOOR |
| | PLAN. 104.2.1 |
| | 5B) SHTS P=2.1 & P-5.6 6" RWL ON FLOOR |
| | PLAN SHOWS 6,150 SF - RISER SHOWS 6,750 |
| | SF. PLEASE CLAIRFY. |
| | 6B) SHTS P-2.1 & P-5.2 RISERS 27 THRU 41 |
| | AT COL. LINE 8 SHOW 300 DFU'S ON FLOOR |
| | PLAN, BUT 370 DFU'S ON RISER. PLEASE |
| | CLAIRFY. 104.2.1 |
| | 7B) SHT P-2.2 POOL DRAIN LINE SHALL |
| | CONNECT TO STORM. |
| | 8B) SHT P-2.2 SHUT OFF VALVE REQUIRED |
| | FOR BLDG WATER SERVICE. 606.1(2) |
| | 9B) SHTS P-2.3 & P-5.5 8" SHOWS 1298 DFU |
| | ON FLOOR PLAN, BUT 1321 DFU ON RISER. |
| | PLEASE CLAIRFY. 104.2.1 |
| | 10B) SHTS P-2.4 & P-5.5 RISER DOES NOT |
| | REFLECT THE FLOOR PLAN. BRANCH TO TOILET |
| | ROOMS CONNECT TO DRAIN AFTER SR128 ON |
| | THE FLOOR PLAN, BUT PRIOR TO SR128 ON |
| | RISER DIAGRAM. PLEASE CLAIRFY. 104.2.1 |
| | 11B) SHTS P-2.4 & P-5.6 FLOOR PLAN SHOWS |
| | 8" @ 10,050 SF, BUT RISER SHOWS 10" @ |
| | 9,450 SF. PLEASE CLAIRFY. 104.2.1 |
| | 12B) SHTS P-2.4 & P-5.6 FLOOR PLAN SHOWS |
| | 1-1/2" CONDENSATE. NOT SHOWN ON RISER. |
| | PLEASE CLAIRFY. 104.2.1 |
| | 13B) SHTS P-2.5 & P-5.6 FLOOR PLAN SF & |
| | RISER SF DO NOT REFLECT.104.2.1 |
| | 14B) SHT P-2/5 SHOWS 4" RWL SHOWS 3,300 |
| | SF UP, BUT 6" RWL DOWN AT 2,7OO SF. |
| | PLEASE CLAIRFY. 6" REQUIRED ON HORIZON- |
| | TAL OFFSETS. TABLE 1106.3 - 104.2.1 |
| | 15B) SUBMIT STORM RISERS. SHOW OFFSETS, |
| | PIPE SIZES, SQUARE FOOTAGE ECT. |
| | 16B) SHT P-2.5 BATHROOM GROUPS SR48 & 49 |
| | NOT SHOWN ON FLOOR PLAN. 104.2.1 |
| | 17B) SHT P-2.5 SR 28 NOT SHOWN ON FLOOR |
| | PLAN. 104.2.1 |
| | 18B) SHTS P-2.6 & P-5.6 FLOOR PLAN DOES |
| | NOT REFLECT THE RISER DIAGRAM. POOL AREA |
| | TRENCH DRAINS NOT SHOWN. 104.2.1 |
| | 19B) SUBMIT CALCULATION FOR RWLS LARGER |
| | THAN 8". TABLE 1106.2 ONLY ADDRESSES |
| | PIPE SIZE TO 8" 104.2.1.2 |
| | 20B) SHTS P-2.6 & P-5.3 FLOOR PLAN SHOWS |
| | SR72 WITH 42 DFU'S AND RISER SHOWS 14 |
| | DFU'S. PLEASE CLAIRFY. 104.2.1 |
| | 21B) SHT P-2.6 ACCUMULATIVE DFU'S APPEAR |
| | TO BE INCORRECT AFTER SR73. PLEASE RE- |
| | CALCULATE. 104.2.1 |
| | 22B) SHT P-2.8 COL LINE 3 BETWEEN COL'S |
| | C & D, A 6" RWL IN 8" CMU WALL NEXT TO |
| | STAIRWAY. PLEASE INDICATE HOW 2 HOUR |
| | FIRE RATING WILL BE MAINTAINED. S-704 |
| | 23B) SHT P-2.8 SIZE SANT PIPE FOR SR9, |
| | SR10, & SR11. TABLE 710.1(2) |
| | 24B) SHTS P-2.9, P-2.10, P-2.11, & P-2. |
| | 12, SANITARY RISER DIAGRAM LOCATIONS NOT |
| | SHOWN. 104.2.1 |
| | 25B) SHT P-4.3 TUB NOT E/03 & TUB AND |
| | LAV NOT VENTED B/11 901.2.1 |
| | 26B) SHT P-4.5 FIXTURES NOT VENTED AND |
| | RISER DOES NOT REFLECT FLOOR PLAN. |
| | 901.2.1 - 104.2.1 |
| | 27B) SHT P-4.6 TUB NOT VENTED AND DOES |
| | NOT REFLECT FLOOR PLAN. 901.2.1/104.2.1. |
| | 28B) SHT P-4.7 TUB NOT VENTED. W/M SHALL |
| | NOT DRAIN THROUGH BATHROOM FIXTURES. |
| | 901.2.1/909.1 |
| | 29B) SHT P-4.9 TUB NOT VENTED. A-13 SEC. |
| | 901.2.1 |
| | 30B) SHT P-4.10 SHOWER NOT VENTED. L-05 |
| | 901.2.1 |
| | 31B) SHT P-4.12 TUB NOT VENTED. A-17 |
| | 901.2.1 |
| | 32B) SHT P-4.13 TUB NOT VENTED. U-1 |
| | 901.2.1 - KITCHEN SINK & WASH MACHINE |
| | SHALL NOT DRAIN THROUGH BATHROOM GROUP |
| | R1(S). 909.1 |
| | 33B) SHT P-4.14 SHOWER NOT VENTED. S1(S) |
| | 901.2.1 |
| | 34B) SHT P-4.15 TUB NOT VENTED. T1 |
| | 901.2.1 |
| | 35B) SHT P-4.17 SHOWER NOT VENTED. S1(N) |
| | 901.2.1. CLAIRFY #10 AND TWO LINES ON |
| | RISER DIAGRAM UPPER LEVEL. AN AAV IS |
| | SHOWN UNDER SINK WITH ANOTHER IN WALL?? |
| | S1(N) |
| | 36B) ALL SANITARY RISER DIAGRAMS. THE |
| | HORIZONTAL BRANCH DRAIN SHALL COMFORM |
| | TO SECTION 917.3.1 OR 917.3.2. SECTION |
| | 917.3. THE HORIZONTAL BRANCH SHALL BE |
| | PROVIDED WITH A RELIEF VENT THAT SHALL |
| | CONNECT TO A VENT STACK, OR A STACK VENT |
| | OR EXTEND OUTDOORS TO THE OPEN AIR. |
| | 37B) ONE SET OF MECHANICAL PLANS HAS RED |
| | LINE INFORMATION. THIS MAY ASSIST IN |
| | EXPLAINING LOCATION & COMMENTS. RETURN |
| | WITH COMMENT RESPONSE WHEN RESUBMITTING |
| | FOR PLAN REVIEW TO HELP EXPEDITE REVIEW. |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |