| Plan Review Notes For Permit 03031778 |
| Permit Number |
03031778 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-09-22 00:00:00 | PLAN DENIED | | | 1) REFER TO SECTION 601.4 BALANCED | | | RETURN AIR (NOTE #12) | | | 2) CAN NOT EXHAUST IN TO WALK WAY M-2.3 | | | 3) CAN NOT BRING IN FRESH AIR FROM | | | LOADING DOCK. | | | 4) GSEF#3 RISER AND PLAN DO NOT MATCH | | | 5) NEED FRESH AIR FOR GYMNAIIUM.FRESH | | | AIR CAN NOT COME FROM GARAGE OR | | | LOADING DOCK. | | | 6) NO EQUIPMENT SCHEDULE FOR RTU# 6,8,9 | | | 10,11,12 | | | PLAN REVIEW BY HAROLD MOSER | | | (561)805-7732 |
|