| 2003-08-29 00:00:00 | 1) SHAFTWAY SIGNS SHALL BE AT LEAST |
| | 6" HIGH. |
| | |
| | 2) KNOX-BOXES WILL BE REQUIRED. |
| | |
| | 3) HOW DOES THE CARD SWIPE DEVICE USED |
| | FOR ACCESS NEAR SAUNA 165 EFFECT |
| | EXITING. |
| | |
| | 4) PLEASE REVIEW ID-12 WHERE THE TRASH |
| | CHUTE OPENS INTO THE CORRIDOR NEAR |
| | THE TOP OF THE PAGE. IT APPEARS THE DOOR |
| | OPENS INTO THE CORRIDOR MORE THAN |
| | 50 PERCENT. |
| | |
| | 5) EXPANDED STYRENE OBSERVED ON A-10.10. |
| | PLEASE SEE APPENDIX F, OF THE LOCAL |
| | AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE. |
| | |
| | 6) LOFT STAIRS ON PAGE A-10.07 ARE |
| | NOT WIDE ENOUGH. IF OCCUPANT LOADS |
| | OF LESS THAN 50 ARE EXPECTED THEN |
| | STAIR CAN BE 36" WIDE. |
| | |
| | 7) FE CABINET ON A-10.07 INDICATES |
| | BREAK GLASS. HOW IS BREAK GLASS DONE. |
| | NO BREAK GLASS ROD SHOWN. |
| | |
| | 8) PLEASE CONFIRM THAT THE EXIT SIGNS |
| | SHOWN ON A-10.03 COMPLIES WITH |
| | CHAPTER 7, OF THE LIFE SAFETY CODE. |
| | |
| | 9) EXTERIOR GRADE PLYWOOD SHOWN ON |
| | SOME ROOF DETAILS. PLEASE SEE APPENDIX |
| | F, OF THE LOCAL AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 10) TRASH CHUTE SECTION MAKES NO |
| | REFERENCE ABOUT FIRE RATED DOORS, |
| | FIRE SPRINKLERS, OR BOTTOM DOOR. |
| | |
| | 11) PLEASE DESCRIBE VOID AREA ON |
| | PAGE A-6.06. |
| | |
| | 12) IT APPEARS THAT THE BUILDING |
| | CAN BE CONSIDERED A HIGH-RISE BUILDING |
| | ACCORDING TO THE BUILDING SECTIONS. |
| | |
| | 13) ITEMS ON THE BUILDING STILL APPEAR |
| | TO PROTECT OVER THE PROPERTY LINES |
| | ACCORDING TO THE BUILDING SECTION |
| | DIAGRAMS. |
| | |
| | 14) IT APPEARS THAT EXITING ON LEVELS |
| | B1 AND B2 PASSES BY IN SOME CASES |
| | PARKING SPACES THAT PERSONS MUST |
| | BACKUP. |
| | |
| | 15) SIGNS WILL BE NEEDED TO IDENTIFY |
| | THE STRETCHER ACCESSIBLE ELEVATORS. |
| | |
| | 16) IT APPEARS THAT THE DOOR AT |
| | GROUND LEVEL FOR STAIR # 3 OPENS |
| | DIRECTLY INFRONT OF A WALL. |
| | |
| | 17) PLEASE INDICATE HOW STAIR # 1 |
| | LEADS DIRECTLY TO THE EXTERIOR. IT |
| | APPEARS TO TERMINATE WITHIN THE |
| | BUILDING. |
| | |
| | 18) IF LESS THAN THREE STEPS ARE PLANNED |
| | FOR A LOCATION, THEN THE MINIMUM TREAD |
| | DEPTH MUST BE AT LEAST 13" WIDE. |
| | |
| | 19) STAIRS THAT FACE CITY STREETS AT |
| | GROUND LEVEL DO NOT APPEAR TO HAVE |
| | HANDRAILS. |
| | |
| | 20) SECOND FLOOR LIFE SAFETY PLAN CHART |
| | INDICATES AN OCCUPANT LOAD OF 560 |
| | PERSONS. YOUR COMMENTS OF 540 OCCUPANTS |
| | ALLOWED AND 526 PERSONS ALLOWED DO |
| | NOT ALIGN THEMSELVES WITH ONE ANOTHER. |
| | |
| | 21) COULD NOT LOCATE ANY STAIRS TO |
| | THE ROOF ON THE ROOF PLAN. |
| | |
| | 22) THE FIRE ALARM ANNUNCIATOR SHOULD |
| | BE INSTALLED NEAR THE MAIN ENTRY DOORS |
| | NOT IN THE FIRE COMMAND ROOM WHERE THE |
| | MAIN PANEL WILL BE LOCATED. |
| | |
| | 23) PLEASE EXPLAIN NOTE # 12 ON FIRE |
| | ALARM SEQUENCE OF OPERATIONS. |
| | |
| | 24) FIRE SPRINKLER PROTECTION WILL |
| | BE REQUIRED TO BE INSTALLED IN THE |
| | RETAIL SPACES OF THE BUILDING PRIOR |
| | TO RECEIVING A C OF O. |
| | |
| | 25) THE FIRE COMMAND ROOM NOTES ON |
| | E-2.5 IS NOT CORRECT. PLEASE SEE |
| | FBC, SECTION 412 FIRE COMMAND ROOMS. |
| | |
| | 26) ALL MECHANICAL, ELECTRICAL, AND |
| | SERVICE ROOMS SHALL BE EQUIPPED WITH |
| | SMOKE DETECTORS. |
| | |
| | 27) NO EXIT SIGNS SHOWN IDENTIFYING |
| | EXIT LOCATIONS FROM POOL AND PLANTER |
| | AREA. |
| | |
| | 28) ALL HOSE VALVES SHALL BE PROVIDED |
| | WITH 2 1/2 TO 1 1/2 REDUCERS. |
| | |
| | 29) WHERE IS THE FIRE PROTECTION FOR |
| | THE UNIT LOWER LEVEL FLOOR PLAN |
| | BETWEEN THE TWO DOORS NEAR THE |
| | HANDICAPPED BATHROOM ON FP-4.10. |
| | |
| | 30) NO STANDPIPE INDICATED ON FP -1.1. |
| | |
| | 31) FDC ON PAGE FP-2.2 IS FACING THE |
| | WRONG WAY. |
| | |
| | 32) UNIT C/17 ON PAGE FP-4.4 DOES NOT |
| | APPEAR TO HAVE ENOUGH SPRINKLER |
| | COVERAGE. |
| | |
| | 33) PLEASE PROVIDE A DIAGRAM FOR |
| | THE SMOKE MANAGEMENT PANEL IN THE |
| | FIRE ALARM CONTROL ROOM. |
| | |
| | 34) STAIRWELL PRESSURIZATION WATER |
| | COLUMN REQUIREMENTS SHALL BE NOTED |
| | ON THE PLANS. ALSO TESTING REQUIREMENTS |
| | SHALL BE DOCUMENTED. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |