| Date |
Text |
| 2003-09-04 00:00:00 | *************** UNSAT ************** |
| | |
| | PLEASE SEE THAT SOME NOTES FROM FIRST |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SHOW POINT OF ATTACHED |
| | FOR TRANSFORMERS. IT IS NOTED ON X-FORM- |
| | -ER SCHEDULE FOR THE SIZE BUT NOT |
| | LOCATION. 250.30 (NOTE#6 FIRST REVIEW) |
| | |
| | 2)NOTE: (NOTE# 1 FIRST REVIEW), RESPONSE |
| | LETTER MENTIONS THAT A NOTE WOULD BE |
| | ADDED TO RISER DIAGRAM. PLEASE CLARFIY/ |
| | SHOW WHERE THIS NOTE IS FOR TEMPORARY |
| | CONDUITS FOR POWER?? |
| | |
| | 3)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS |
| | WHAT APPEARS TO BE ONE BUS-DUCT COMING |
| | FROM FPL FEEDINGMAINS 1 AND 2? |
| | PLEASE SEE RISER NOTES: MENTIONS BUS |
| | DUCT TO BE 3000A'S AND LOAD ON BOTH OF |
| | THESE MAINS EXCEED RATING OF 3000A DUCT? |
| | PLEASE CLARIFY IF THESE ARE TO BE |
| | SEPARATE? 215.5 |
| | |
| | 4)NOTE: PLEASE SEE E6.1, SHOWS TWO |
| | MC-"B"'S, APPEARS TO BE A MISPRINT? |
| | |
| | 5)NOTE: PLEASE SEE RISER DIAGRAM NOTES, |
| | MENTIONS 1 1/2" CONDUIT FOR 3-3/0'S AND |
| | 1-#6. PLEASE SEE CONDUIT FILL TABLES IN |
| | NEC. CHPT 9 |
| | |
| | 6)NOTE: PLEASE CORRELATE ALL PAGES, |
| | MAINLY E2.7 AND 3.1, FOR FUEL ALARMS, |
| | ONE MENTION 80% AND 90% AND OTHERS |
| | MENTION 85 AND 95%. |
| | |
| | 7)NOTE: PLEASE SEE NOTE FROM FIRST |
| | REVIEW FOR GFI PROTECTION REQ'D FOR |
| | HDP. RESPONSE LETTER MENTIONS THAT |
| | INDICVATION WOULD BE MADE LARGER? |
| | PLEASE CLARIFY WHERE THIS IS. PANEL |
| | SCHEDULE DOES NOT MENTION AND RISER |
| | IS NOT CLEAR. PLEASE INDICATE AT BOTH |
| | LOCATIONS,RISER AND PANEL. |
| | 230.95/215.10 ETC. |
| | |
| | 8)NOTE: PLEASE SEE DISCONNECT SHOWN ON |
| | RISER DIAGRAM FOR X-FORMER TP, THERE IS |
| | NO INFORMATION GIVEN FOR SIZE,OCP ETC, |
| | PANEL SCHEDULE FOR HDP MENTIONS TO |
| | FEED X-FORMER TP W/ 200A OCP, YET |
| | X-FORMER SCHEDULE MENTIONS 100A OCP? |
| | PLEASE CLARIFY AND PROVIDE MORE INFOR. |
| | 215.5 |
| | |
| | 9)NOTE: PLANS INDICATE ON 1.2 TO SEE |
| | 3.1 FOR ENLARGED ELECTRICAL RM LAYOUT |
| | FOR REQ'D ELECTRICAL. PLEASE CLARIFY |
| | WHERE LIGHTING/POWER IS SHOWN? MINLTS |
| | ALSO PER 700.16, PLEASE ALSO SEE FIRE |
| | REVIEW NOTES FOR POSSIBLE REQ'D SD IN |
| | ELECTRICAL RM. |
| | |
| | 11)NOTE: PLEASE SEE 110.26C FOR ENTRANCE |
| | INTO AND OUT OF ELECTRICAL RM. |
| | PLEASE SEE THE EXCEPT.'S |
| | PER SCALE, IT DOES NOT SEEM TO MEET |
| | TWICE THE DISTANCE ACCROSS FOR CLEARENCE |
| | ? PLEASE CLARIFY AND/OR ADJUST. |
| | |
| | 12)NOTE: PLEASE SEE 210.52 FOR RECEPTS |
| | SPACING. THERE ARE MANY UNITS MISSING |
| | RECEPTS FOR 2' OF WALL ETC. |
| | ON SET OF PLANS HAVE SOME OF THESE AREAS |
| | REDLINED. F.R> |
| | |
| | 13)NOTE: PLEASE ALSO SEE 210.52C-1 FOR |
| | RECEPTS REQ'D FOR COUNTERSPACE, THERE |
| | ARE ONLY A COUPLE MISSING, SEE UNIT D36. |
| | F.R. |
| | 14)NOTE: PLEASE SEE NOTE#22 FROM FIRST |
| | REVIEW. RESPONSE LETTER MENTIONS, UNIT |
| | IS 800 SQ FT AND WILL COMPLY? PLEASE SEE |
| | D36, PANEL SCHEDULE SHOWS UNIT AT 1059SQ |
| | FT?? PLEASE SEE OTHER UNITS THAT ARE |
| | LARGER AND NO CHANGE WAS MADE> |
| | PLEASE ALSO SEE SQFT FOR ALL OTHER UNITS |
| | SOME DO NOT SEEM TO CORRELATE W/SCALE? |
| | |
| | 15)NOTE: PLEASE SEE NOTE 26 FROM FIRST |
| | REVIEW, RESPONSE MENTIONS, WILL COMPLY. |
| | PLANS DO NOT SEEM TO HAVE AHD SD'S |
| | MOVED OR NOTE ADDED FOR INSTALLATION OF |
| | SD'S? NFPA-72 |
| | |
| | 16)NOTE: PLEASE SEE NOTE#36 FR> RESPONSE |
| | MENTIONS; WILL COMPLY, HOWEVER PANELS |
| | STILL DO NOT INDICATE SPECS ON PANELS, |
| | SIZE? THEY ARE NOTED WITH SIZE OF FEEDER |
| | -S. 215.5 |
| | |
| | 17)NOTE: PLEASE SEE NOTE#27 , PLEASE |
| | SEE SOME UNITS MOVED RECEPTS TO COMPLY, |
| | HOWEVER PLEASE SEE SOME UNIT(S), THERE |
| | ARE MANY UNITS STILL NEED TO MEET |
| | 210.52D, TO BE W/IN 3' OF LAV/SINKS. |
| | |
| | 18)NOTE: PLEASE SEE NOTE#39 ,PLEASE |
| | CLARIFY WHERE NOTE IS FOR COLOR CODING |
| | OF CONDUCTOR PER LOCAL AMENDMENTS? |
| | 215. 277/480V BROWN/PURPLE/YELLOW |
| | |
| | PLEASE SEE FIRE REVIEW COMMENTS AND |
| | COMMENTS FROM OTHER REVIEWERS THAT MAY |
| | HAVE AN AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW.IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2003-09-03 00:00:00 | NOTES TO FOLLOW, |