| 2005-12-19 00:00:00 | ******* UNSAT ******** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES DUE TO |
| | INFORMATION ADDED TO PLANS. |
| | |
| | |
| | |
| | 1)NOTE: PLEASE SEE MIN CLEARENCE |
| | REQUIREMENTS FOR MAIN ELECTRICAL ROOM. |
| | PLEASE ALSO SEE THAT A MIN 6' OPENING |
| | AND DOUBLE WORKING SPACE. |
| | THIS WAS NOTED AS BEING CORRECTED , |
| | HOWEVER PLANS STILL SHOWN WITH OUT |
| | CHANGES MADE. |
| | 110.26 |
| | |
| | 2)NOTE: PLEASE SEE V-33 RM W/O RECEPTS, |
| | PLEASE SEE OTHER LOCATIONS ON NUMEROUS |
| | UNITS MISSING RECEPTS REQUIRED PER |
| | 210.52 |
| | PLEASE SEE REDLINED PLANS. |
| | |
| | 3)NOTE: PLEASE SEE V-33, PLEASE |
| | CORRELATE THE NUMBER OF COMPLETE A/C |
| | SYSTEMS ON SCHEDULE, LOAD CALCS AND |
| | PLANS. |
| | SHOWS TWO, ONE AND ONE. |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE COMPLETE ROOM AND AREA |
| | DESIGNATIONS ON PLANS. PLEASE SEE |
| | REDLINED PLANS FOR UNITS INCOMPLETE AT |
| | THIS TIME. SOME FROM PREVIOUS REVIEW |
| | WERE DONE. |
| | 215.5 |
| | NEED TO VERIFY, PLEASE SEE NEXT COMMENT. |
| | |
| | 5)NOTE: PLEASE SEE MANY DINING RM AREAS |
| | WHICH INDICATE 15A, #14 AWG FOR DINING |
| | RM CIRCUIT. |
| | PLEASE SEE 210.52B1, 210.11C |
| | MUST BE 20A AND #12. |
| | D36,28, G14, H10 ETC |
| | |
| | 6)NOTE: PLEASE SEE UNIT J-12, UNIT WALLS |
| | NOT COMPLETE 210.52 |
| | PLEASE ALSO SEE SD'S ON TWO CIRCUITS. |
| | PLEASE SEE NFPA-72 WHICH REQUIRES SD'S |
| | TO BE WIRED "INLINE". |
| | |
| | 7)NOTE: PLEASE SEE MISSING DOORS ON |
| | UNITS C-21, J-12ETC. |
| | |
| | 8)NOTE: PLEASE SEE MANY UNITS WHERE SD'S |
| | ARE MISSING THE CIRCUITING NUMBERS, NEED |
| | TO VERIFY. |
| | 215.5, NFPA-72 |
| | |
| | 9)NOTE: PLEASE SEE REDLINED PLANS FOR |
| | MISSING GFI RECEPTS PER 210.52C1, SEEMS |
| | TO BE ONLY A COUPLE AT THIS TIME. |
| | S1(S), |
| | |
| | 10)NOTE: PLEASE CORRELATE THE NUMBER OF |
| | SM APPL CIRCUITS ON PLANS, PANEL |
| | SCHEDULE AND LOAD CALCS. A-13 |
| | |
| | 11)NOTE: PLEASE SEE MANY UNITS WHERE |
| | MORE THEN ONE BATHROOM IS ON THE SAME |
| | CIRCUIT. THIS INLCUDES , RECEPTS AND |
| | LIGHTS ON SAME CIRCUIT, HOWEVER THIS |
| | CIRCUIT ALSO FEEDS OTHER BATHROOMS. |
| | PLEASE ALSO SEE BATH CIRCUIT ON WITH |
| | LIVING RM. |
| | PLEASE SEE A17, U-1, R1(S) S1(S) Q1, |
| | R1,(N) ETC ETC. |
| | MOST OF THESE ARE REDLINED. |
| | PLEASE SEE 210.52D, AND 210.11C3, WHICH |
| | PERMITS EITHER MORE THAN ONE BATH GFI ON |
| | THE SAME CIRCUIT, BUT MUST NOT HAVE ANY |
| | LIGHTING OR OTHER LOADS ON THAT 20A,#12 |
| | GFI CIRCUIT, OR |
| | BATH GFI AND LTS MAY ON TOGETHER, BUT |
| | SHALL NOT FEED ANY OTHER RECEPTS,LTS OR |
| | OTHER LOADS OUTSIDE THAT PARTICULAR |
| | BATHRM. |
| | |
| | 12)NOTE: PLEASESEE MIN CLEARENCE FOR |
| | CLOASET LT IN UNIT S1(N), 410.8 |
| | |
| | 13)NOTE: PLEASE INDICATE THE GROUNDING |
| | ELECTRODE SYSTEM FOR GENERATOR. |
| | 250.30 |
| | |
| | 14)NOTE: PLEASE VERIFY BASEMENT SUMP |
| | PUMPS COMING FROM THE NON-EMERGENCY OF |
| | HOUSE POWER. |
| | THIS IS NOT AN ELECTRICAL NEC CODE |
| | COMMENT, ONLY TO VERIFY. |
| | |
| | ** PLEASE SEE MANY OF THE ABOVE ITEMS |
| | ARE REDLINED ON PLANS FOR AREAS OF |
| | COMMENTS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW AND IF THEREARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |