| 2005-07-12 00:00:00 | ELECTRICAL REVISIONS DATED 6/6/05 |
| | |
| | *********** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE MIN OPENINGS AND |
| | OPENING SIZES FOR ELECTRICAL ROOMS. |
| | PLEASE SEE MAIN ELECTRICAL ROOM HAD |
| | CHANGED AND NO REVISION IS SHOWN FOR |
| | 110.26 |
| | THIS WAS GONE OVER DURING A WALK THROUGH |
| | AT SAID PROJECT A FEW MONTHS BACK. |
| | |
| | 2)NOTE: PLEASE LABEL AND INDICATE ALL |
| | MAINS ON ELECTRICAL ROOM PLANS AND ON |
| | RISER. |
| | PLEASE ALSO SEE METER-CENTER "A" IS |
| | SHOWN AS MAIN #1?? |
| | |
| | 3)NOTE: PLEASE SEE NUMEROUS RECEPTS |
| | REQUIRED PER 210.52 HAVE NOW BEEN |
| | REMOVED FROM PLANS. |
| | THESE WERE ON ORIGINAL PLANS. |
| | THIS WAS GONE OVER WITH ELECTRICAL |
| | CONTRACTOR, GEN CONTRACTOR, ENGINEERING |
| | STAFF AT JOBSITE WHICH THE DECISION THAT |
| | ALL RECEPTS ARE REQUIRED AND SHALL BE |
| | INSTALLED. MANY OF THESE HAVE NOW BEEN |
| | REMOVED FROM PLANS?? |
| | |
| | 4)NOTE: PLEASE SEE MISSING RECEPTS IN |
| | MANY UNITS REQUIRED PER 210.52C1-5 |
| | |
| | 5)NOTE: PLEASE SHOW ALL RECEPTS REQUIRED |
| | TO BE GFI/GFI PROTECTEDON PLANS. |
| | PLEASE SEE KITCHEN COUNTERSPACES, BATHS |
| | ETC. 210.8A6, 210.8A3 |
| | |
| | 6)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULES |
| | SUBMITTED FOR UNITS. PLEASE ALSO SEE |
| | OTHER NOTES; |
| | |
| | 7)NOTE: PLEASE CORRELATE CIRCUITS; SOME |
| | SHOWN ON PLANS, HOWEVER PANEL SCHEDULE |
| | INDICATES THESE CIRCUITS AS A |
| | "SPACE"/"SPARE". |
| | PLEASE SEE MIN SMALL APPLIANCE CIRCUITS, |
| | SOME CIRCUITS SHOWN FOR FRIG IS ALSO |
| | SMALL APPL ETC. |
| | |
| | 8)NOTE: PLEASE SEE OSME UNITS NO LONGER |
| | CONTAIN ROOM DESIGNATIONS? |
| | PLEASE SHOW. |
| | |
| | 9)NOTE: PLEASE SEE MANY OF THE |
| | ELECTRICAL PANELS ARE SHOWN AS 120A?? |
| | PLEASE SEE SOME ARE HAVE 125A FEEDS AND |
| | SOME HAVE 200A FEEDS. BOTH OF WHICH ARE |
| | ON 120A(?) PANELS. |
| | |
| | 10)NOTE: PLEASE SOME UNITS INDICATE TWO |
| | A/C SYSTEMS , HOWEVER LOAD CALCUALTIONS |
| | DO NOT SEEM TO CORRELATE WITH NUMBER OF |
| | A/C UNITS AND LOADS. |
| | PLEASE SHOW KW RATINGS FOR EACH AHU ON |
| | ALL PANEL SCHEDULES. |
| | PLEASE ADJUST ALL. |
| | |
| | 11)NOTE: PLEASE SEE COMPLETE SHIFT OF |
| | ELECTRICAL ONC/21. |
| | |
| | 12)NOTE: PLEASE SEE RISER NOW SHOWS A |
| | NEW PANEL "B", HOWEVER NO INFORMATION ON |
| | PANEL OR PANEL SCHEDULE WAS SUBMITTED. |
| | PLEASE SEE 240.21,408.16 ETC? |
| | |
| | 13)NOTE: PLEASE CORRELATE FEEDERS ON |
| | RISER WITH FEEDERS ON HEDP FOR SC. |
| | |
| | 14)NOTE: PLEASE VERIFY DEDICATED |
| | CIRCUITS FOR EACH OF THE ELEVATOR |
| | MACHINE RMS 620.23,24 |
| | |
| | 15)NOTE: PLEASE VERIFY CIRCUITING OF |
| | EGRESS PATHS IN HALLWAYS AND STAIRWELLS. |
| | ALTERNATING CIRCUITS OR POSSIBLE BATTERY |
| | BACK UP FIXTURES. |
| | LS 101 7-9 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |