| 2004-08-07 00:00:00 | REVISION DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FHA-98 DESIGN MANUAL |
| | |
| | 1) THESE REVISIONS ARE SHOWING NEW REV- |
| | ISION NUMBERS AND THESE REVISION PLANS |
| | ARE NOT CHECKED FOR PREVIOUS REVISIONS |
| | THAT MAY OR MAY NOT HAVE BEEN OMITTED OR |
| | RETAINED. SECTION 104.2.1 |
| | 2) SEPARATE PERMIT REQUIRED FOR FOUNTAIN |
| | SHOWN ON SHEETS F1 & F2. |
| | 3) SHT A-3-2AB MISLABELED AS A-3-2AE. |
| | SECTION 104.2.1 |
| | 4) SHEET AFTER A-3-4BC HAS NO SHEET NUM- |
| | BER AND FIXTURES HAVE BEEN DELETED. NO |
| | W/C OR LAV SHOWN. SECTION 104.2.1 |
| | 5) SHT A-3-4CD INDICATE DEPTH OF DRYWELL |
| | SECTION 104.2.1. |
| | 6) NUMEROUS ARCHITECTURAL SHEETS HAVE |
| | WHITE OUT DELETING BATHROOM TYPE AND "B" |
| | WRITTEN IN. THIS IS NOT APPROVED. MAKE |
| | ALL CHANGES WITH NEW SHEETS SIGNED/SEAL- |
| | ED & DATED BY ARCHITECT OF RECORD. SECT- |
| | ION 104 104.2.1.3. |
| | 7) SHT A-4.18 BATHROOM TYPE IS NOT SHOWN |
| | AS REQUIRED BY FHA DESIGN MAN. REQUIRE- |
| | MENT #7B |
| | 8) SHTS P-2.4 & P-5.5 FLOOR DRAIN ADDED |
| | TO TRASH ROOM SHT P-2.4 IS NOT SHOWN ON |
| | THE BLDG. SANT. RISER DIAGRAM SHT P-5.5 |
| | SECTION 104.2.1 |
| | 9) SHTS P-2.5, P-5.5 & P-5.6, BLDG. SANT |
| | RISER DIAGRAM DOES NOT REFLECT CHANGES |
| | IN FLOOR PLAN. ALSO RISER SR/58 IS NOT |
| | SHOWN ON BLDG. SANT. RISER. - BLDG. |
| | STORM RISER DOES NOT REFLECT CHANGES OF |
| | SHT P-2.5, MISSING PIPE SIZES, SQUARE |
| | FOOTAGE, AND LAYOUT CHANGES. SEC 104.2.1 |
| | 10) SHTS P-2.6, P-5.5 & P-5.6 RISERS DO |
| | NOT REFLECT CHANGES IN FLOOR PLAN. PIPE |
| | SIZES, SQUARE FOOTAGE, LAYOUT CHANGES. |
| | SECTION 104.2.1. |
| | 11) SHTS P-4.1 THRU P-4.18 & SHTS P-5.1, |
| | P-5.2, P-5.3, P-5.3.1, & P-5.3.2. UNIT |
| | TYPES WASTE & VENT RISERS SHOW BRANCH |
| | LINES TO FIXTURES CONNECTING TO THE |
| | STACK ON THE SAME FLOOR AS THE FIXTURES. |
| | (WASTE STACK) - BUT RISER DIAGRAMS SHOW |
| | CONNECTIONS TO THE STACK ON THE FLOOR |
| | BELOW CREATING AN "S" TRAP NOT APPROVED |
| | BY SECTION SECTION 1002.3. PLEASE CLARI- |
| | FY. SECTION 104.2.1 |
| | 12) SHT P-5.6 SIZE PIPE FRON TRENCH |
| | DRAINS TO DRAINAGE STRUCTURE AND SHOW |
| | TOTAL SQUARE FEET. SECTION 104.2.1 |
| | ALSO THE OTHER 3 REVISION AREAS HAVE NO |
| | CHANGES FROM PREVIOUS REVIEW DATED |
| | 2-12-4. |
| | 13) SHT P-5.5 GAS ISOMETRICS - MEASURE- |
| | MENTS FOR CUT SECTIONS OF PIPE WERE DE- |
| | LETED FROM STAMPED SET OF PLANS. THESE |
| | MEASUREMENTS ARE REQUIRED ON PLANS. |
| | SECTION 104.2.1 AND FUEL GAS CODE. |
| | |
| | REVIEW BY KEN STEVENS |