| Plan Review Notes For Permit 03031778 |
| Permit Number |
03031778 |
|
| Review Stop |
FIRE |
| Sequence Number |
10 |
|
| Notes |
| Date |
Text |
| 2005-02-08 00:00:00 | 1. FDC SHOWN ON C-32 SHOULD FACE | | | DATURA STREET. THE POSITION SHOWN | | | ON C-32 WATER SERVICE DETAIL WILL | | | CAUSE THE HOSE TO KINK WHEN | | | CONNECTED TO IT. | | | | | | 2. ALL EXIT STAIRS SHALL SWING IN THE | | | DIRECTION OF EXIT TRAVEL. | | | | | | 3. ALL EXITS SHALL COMPLY WITH | | | THE LIFE SAFETY CODE, APPROPRIATE | | | EDITION. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|