| Date |
Text |
| 2003-04-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FHA-98 DESIGN MANUAL |
| | CITY WPB CODE |
| | |
| | 1) SHT C2.1 CONTROL STRUCTURE, SHOWS 15" |
| | INLET FROM RAIN WATER LEADERS, BUT NO |
| | INLET FROM EXFILTRATION TRENCH. PLEASE |
| | CLAIRFY. |
| | 2) SHT C2.1 DRAINAGE STRUCTURE, SHOWS |
| | 24" FROM CONTROL STRUCTURE & 18" TO THE |
| | TRENCH. PLEASE CLAIRFY. |
| | 3) SHT C-2.0 EMERGNECY OVERFLOW FROM THE |
| | CONTROL STRUCTURE DRAINS BY SUMP VAULT. |
| | THE SUMP PUMP THEN DRAINS TO CONTROL |
| | STRUCTURE. PLEASE CLAIRFY |
| | 4) SHT L-5.1 RAIN SENSOR REQUIRED. ALSO |
| | SEPARATE IRRIGATION PERMIT REQUIRED. |
| | 5) SHT L-5.4 RPZ BACKFLOWS ARE REQUIRED |
| | FOR EXTERNAL IRRIGATION. |
| | 6) SHT F1 BACKWASH SHALL DRAIN TO SANT. |
| | 7) SHT A-4.01 DETAIL #1 CLEAR FLOOR |
| | SPACE REQUIRED FOR ALL FIXTURES PER FHA- |
| | DESIGN MANUAL PAGE 7.43 (ALL UNITS) |
| | 8) SHT A-4.01 DETAIL #4 LAV ELEVATION, |
| | MAXIMUM 34" TO LAV PER FHA DESIGN MANUAL |
| | PAGE 7.52 (ALL UNITS) |
| | 9) SHT A-4.01 DETAIL #5 TUB BACKING, PER |
| | FHA DESIGN MANUAL PAGE 6.9 (ALL UNITS) |
| | 10) SHT A-4.01 DETAIL #6, SHOW SIDE RE- |
| | INFORCEMENT PER FHA DESIGN MANUAL PAGE |
| | 6.5 (ALL UNITS) |
| | 11) SHT A-4.01 DETAILS REFER TO SHT A-XX |
| | BUT SHT A-XX NOT FOUND. PLEASE CLAIRFY. |
| | 12) SHT A-10.02 DETAIL #2 SCUPPER, SHOW |
| | WIDTH & HEIGHT. SCUPPER SHALL BE INSTALL |
| | ED PER SECTION 1503.4.2. SHOW HEIGHT |
| | TO FLOW LINE OFF ROOF |
| | 13) PLEASE IDENTIFY ALL WORK/LIVE LOFTS. |
| | TOILET ROOMS SHALL COMPLY WITH 11-4.22. |
| | ALL UNITS SHALL HAVE A DRINKING FOUNTAIN |
| | PER TABLE 403.1. (ALSO SEE 410.1) |
| | 14) SHT P-1.2 GREASE TRAPS TO BE SIZED |
| | BY RODNEY COMPO, ENVIRONMENTAL COMPLIAN- |
| | CE. UTILITY ORD #2938-96. PLEASE CONTACT |
| | @ (561) 837-4074. |
| | 15) SHT P-1.3 15" STORM @ 53,900 SQ. FT. |
| | SHALL BE RUN AT A MINIMUM OF 1/4" PER FT |
| | PLEASE INDICATE ON PLANS. |
| | 16) SHTS P2.1/P2.2 SEPARAGE GAS PERMIT |
| | REQUIRED. THE FOLLOWING INFORMATION IS |
| | REQUIRED PRIOR TO PERMIT ISSUANCE. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). (REQUIRED AT BUILDOUT) |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. (REQD AT BUILDOUT) |
| | F. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. (REQD. AT BUILD0UT) |
| | G. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. (IF LP) |
| | H. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). (IF LP) |
| | I. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. (REQD AT |
| | BUILDOUT) |
| | PLEASE PROVIDE THE TABLE THAT WAS USED |
| | TO SIZE PIPE FOR 8500 CFH @ 500 FEET. |
| | PLEASE INDICATE WHO PROVIDES TABLE REF- |
| | ERENCED. (TABLE NEEDS TO BE APPROVED) |
| | ---SUGGESTION--- A 2LB SYSTEM OR A 5LB |
| | SYSTEM WILL ENABLE THE SYSTEM TO USE A |
| | SMALLER SIZE SUPPLY PIPE-------- |
| | 17) SHT P-2.2 6" RPZ BACKFLOW PREVENTER |
| | SHALL BE LOCATED A MAXIMUM OF 4 FT ABOVE |
| | THE FLOOR FOR SERVICING AND TESTING. |
| | 18) SHT P-2.4 CONDENSATE IS NOT ALLOWED |
| | TO DRAIN INTO SANITARY SYSTEM. CITY CODE |
| | 90-125(B)(5). |
| | 19) SHTS P-2.25/.26/.26/.28 & A-2.11 |
| | SUBMIT CALCULATIONS FOR PRIMARY AND SEC- |
| | ONDARY ROOF DRAINS. SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS. SHOW |
| | ALL AREA OF ROOFS THAT DRAIN DOWN ON THE |
| | ROOF FROM ABOVE. SHOW LOCATION OF ALL |
| | SECONDARY OVERFLOW DRAINS OR SCUPPERS. |
| | SECTIONS 1106 & 1107 AND ALL SUBSECTIONS |
| | 20) SHT P-2.8 CONDENSATE SHALL RUN SEP- |
| | ARATELY OUT OF BLDG OR TO CATCH BASINS. |
| | PLEASE PROVIDE SEPARATE CONDENSATE IS0- |
| | METRIC RISER. SHOW BLDG COND. DRAIN AND |
| | ALL RISERS AND INDICATE LOAD AS IT ACCU- |
| | MULATES. |
| | 21) SHT P-4.1 SANITARY RISER DOES NOT |
| | REFLECT THE FLOOR PLAN. KITCHEN SINK |
| | SHALL NOT DRAIN INTO THE WET VENT OF THE |
| | BATHROOM GROUP. 909.1 - THE KITCHEN SINK |
| | SHALL DRAIN DOWNSTREAM OF THE BATHROOM |
| | GROUP. - TUB NEEDS TRAP. |
| | 22) SHT P-4.2 SANT. RISER DOES NOT RE- |
| | FLECT FLOOR PLAN. H/10 & J/12 |
| | 23) SHT P-4.4 SANT. RISER DOES NOT RE- |
| | FLECT FLOOR PLAN. C-21 |
| | 24) SHT P-4.6 SANT. RISER DOES NOT RE- |
| | FLECT FLOOR PLAN. P/36 |
| | 25) SHT P-4.7 SANT. RISER DOES NOT RE- |
| | FLECT FLOOR PLAN. N/03 |
| | 26) SHT P-4.7 SANT. RISER DOES NOT RE- |
| | FLECT FLOOR PLAN. F/28 - KITCHEN SINK |
| | SHALL NOT DRAIN THROUGH WET VENTED BATH- |
| | ROOM GROUP 909.1. KIT. SINK SHALL DRAIN |
| | DOWNSTREAM OF BATHROOM GROUP. |
| | 27) SHT P-4.9 SANT RISER DOES NOT RE- |
| | FLECT FLOOR PLAN.WASH MACHINE & KIT. |
| | SINK SHALL DRAIN DOWNSTREAM OF BATHROOM |
| | GROUP. 909.1D/28 - D/36 |
| | 28) SHT P-4.9 SANT. RISER DOES NOT RE- |
| | FLECT FLOOR PLAN A13. NO SANT LINE TO |
| | WATER CLOSET ON FLOOR PLAN. |
| | 29) SHT P-4.12 NO SANITARY LINE TO WATER |
| | CLOSET ON LOWER FLOOR PLAN. |
| | 30) SHT P-4.16 WATER RISER DOES NOT RE- |
| | FLECT FLOOR PLAN. |
| | 31) SHTS FOR ALL UNITS, WATER HAMMER |
| | ARRESTOR REQUIRED AT ICE MAKER LINE IN |
| | ALL UNITS. PLEASE REVISE. |
| | 32) SHT P-4.17 SANT. RISER DOES NOT RE- |
| | FLECT THE FLOOR PLAN. |
| | 33) SHT P-4.18 SANT. RISER 909.1 KITCHEN |
| | SINK SHALL NOT DRAIN INTO WET VENT FOR |
| | BATHROOM GROUP. |
| | 34) SHT P-5.1 RISER SR4 N/203/(19) DFU |
| | NOT ADDED TO TOTAL FOR RISER. |
| | 35) SHT P-5.3 RISER SR15 SHOWS 123 DFU, |
| | ACTUALLY 133 DFU. |
| | 36) SHT P-5.4 DETAIL #5 PLEASE SHOW SIZE |
| | OF SUPPLY TO URNAL. |
| | 37) SHT P-5.4 DETAIL #1 RPZ BACKFLOW TO |
| | BE MAX. 4' ABOVE FLOOR FOR SERVICING AND |
| | TESTING. |
| | 38) SHT P-5.4 DETAIL #1 RPZ BACKFLOW RE- |
| | QUIRED FOR FOUNTAIN WATER SERVICE. |
| | 39) SHT P-5.5 RISERS #'S 39, 40, 41, 42, |
| | 43, 44, & 45 NOT FOUND. PLEASE SUBMIT |
| | INFORMATION ON THESE RISERS. |
| | 40) SHT P-5.5 INDICATES DETAIL FOR |
| | GREASE TRAP ON SHT P-7.1, BUT NO DETAIL |
| | WAS FOUND. SEE ATTACHED SHEET FOR APP- |
| | ROVED GREASE TRAP DETAIL. SUBMIT ON PLAN |
| | NOTE 2-WAY CLEAN OUTS REQD. ENTERING & |
| | EXITING EACH GREASE TRAP. |
| | 41) SHT P-5.5 CORRECT ALL AREAS WHERE |
| | RED LINED. SHOW ALL PIPE SIZES AND DFU |
| | NOT SHOWN. |
| | 42) SHT P-5.5 DFU'S FROM GREASE TRAP NOT |
| | ADDED TO SYSTEM. RECALCULATE DFU'S. SHOW |
| | SLOPE OF PIPE ON RISER DIAGRAM. |
| | 43) SHT P-5.6 CONDENSATE RISER SHALL NOT |
| | TERMINATE IN A/C ROOM IF USED AS A PLEN- |
| | UM. |
| | 44) SHT P-5.6 6" @ 6150 SQ FT NOT APP- |
| | ROVED. MINIMUM OF 1/4" PER FT OR LARGER |
| | SIZE PIPE. PLEASE SHOW SLOPE OR INCREASE |
| | PIPE SIZE. |
| | 45) SHT P-5.6 5" REQUIRED @ 1950 SQ FT. |
| | 46) SHT P-5.6 SHOW AREA DRAINED AT 4" |
| | TRENCH DRAINS ON RISER DIAGRAM. |
| | 47) SHT P-5.6 SHOW PIPE SIZE FOR ENTRY |
| | TRENCH DRAINS ON RISER. |
| | 48) SHT P-5.6 STORM ISOMETRIC, 15" PIPE |
| | DRAINING 61,089 SQ FT SHALL BE MINIMUM |
| | OF 1/4" PER FOOT. PLEASE INDICATE ON |
| | RISER. |
| | 49) SHT P-5.6 PLEASE INDICATE MATERIAL |
| | FOR RELIEF VALVE & EMERGENGY PAN DRAIN |
| | RISERS. (PVC NOT APPROVED) |
| | 50) SHT P-6.1 CONDENSATE SHALL RUN SEP- |
| | ARETELY. (SEE COMMENT #20) |
| | 51) SHT P-6.1 PLUMBING FIXTURE SCHEDULE, |
| | HANDICAP WATER CLOSET TO BE 17" TO 19" |
| | TO SEAT. 11-4.16.3 |
| | 52) SHT P-6.1 PLUMBING FIXTURE SCHEDULE, |
| | 6" ROOF DRAIN, VENT NOT REQUIRED. TRAP |
| | NOT APPROVED. |
| | SHT P7.1 AIR CHAMBER DETAIL, AIR CHAMB- |
| | ERS ARE NOT APPROVED. PLEASE DELETE DE- |
| | TAIL. |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |