| 2003-04-15 00:00:00 | PLEASE SEE COMMENTS STARTED 4/14 AND |
| | COMPLETED 4/15/03 |
| 2003-04-14 00:00:00 | ************* UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE PROVIDE NOTE ON ELECTRIC- |
| | -AL RISER DIAGRAM: ELECTRICAL CONTRACTOR |
| | TO PROVIDE SPARE CONDUITS TO ANY |
| | PANELS AND/OR EQUIPMENT THAT MAY NEED TO |
| | BE FED FROM TEMPORARY POWER BEFORE |
| | MAIN SERVICE IS RELEASED ON BLDG. |
| | PLEASE ALSO NOTE: TEMPORARY SERVICE MUST |
| | BE OF ADEQUATE SIZE. |
| | |
| | 2)NOTE: PLEASE SEE DOUBLE PRINT ON TITLE |
| | BLOCK FOR ENGINEER OF RECORD. PLEASE |
| | REPRINT FOR CLARITY. FAC 61G15-23.002 |
| | |
| | 3)NOTE: PLEASE SUBMIT AND SHOW AIC |
| | RATINGS FOR ALL NEW EQUIPMENT BEING |
| | INSTALLED. MAINS/PANELS/BREAKERS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT. PER 110-9 IT IS NOTED, ELECTRI- |
| | -CAL CONTRACTOR TO PROVIDE SIGNED AND |
| | SEALED SHOP DRAWINGS FOR THIS. |
| | PLEASE NOTE, THIS MUST BE SUBMITTED WITH |
| | PLANS FROM THE ENGINEER OF RECORD. |
| | |
| | 4)NOTE: PLEASE SEE E3.1. GENERATOE SHOWN |
| | AS 600W? PLEASE CORRELATE W/ RISER |
| | DIAGRAM. |
| | |
| | 5)NOTE: PLEASE SHOW(MAP) LOCATION AROUND |
| | FUEL FILL AREA REMOTE FROM GENERATOR |
| | PER NEC 500. |
| | |
| | 6)NOTE: PLEASE SHOW/LIST GROUNDING FOR |
| | ALL TRANSFORMERS PER 250-30 |
| | |
| | 7)NOTE: PLEASE SEE E3.1, SHOWS 2-4" |
| | CONDUITS FOR 400A SE RATED SWITCH, |
| | PLEASE SEE RISER, SHOWS ONLY ONE CONDUIT |
| | FROM FPL.? PLEASE CORRELATE. |
| | |
| | 8)NOTE: PLEASESUBMIT/SHOW MORE ON |
| | SERVICE FOR FUTURE TENANT SPACES. |
| | SERVICE, MAINS ETC? |
| | PLEASE CLARFIY IF 400A SE RATED MAIN IS |
| | FOR FUTURE TENANTS? |
| | |
| | 9)NOTE: PLEASE SEE CODE REFERENCED FOR |
| | GROUNDING ELECTRODE IS FROM THE 96 NEC. |
| | (250-81) PLEASE NOTE:250-66 99NEC |
| | |
| | 10)NOTE: PLEASE NOTE, AS PER PLANS, |
| | MAINS IN BLDG ARE NOT GROUPED. PLANS |
| | ARE SHOWING 13 MAINS IN BLDG WHICH DOES |
| | NOT INCLUDE FIRE PUMP.230-2/230-70, |
| | 230-72, 225-38 ETC. |
| | MAINS ARE TO BE LOCATED AT THE NEAREST |
| | POINT OF ENTRANCE TO A BLDG.E |
| | PLEASE ALSO NOTE, FIRE AND LIFE SAFTEY |
| | ISSUES COME INTO PLAY W/ THE MAJOR |
| | TRAVEL DISTANCES AND NUMEROUS LOCATIONS |
| | TO TURN POWER OFF IN BLDG. |
| | PLEASE ALSO NOTE, SERVICES CROSSING |
| | EACH OTHER, AND/OR HOUSE (277/480V) |
| | POWER. |
| | |
| | 11)NOTE: PLEASE CLARIFY HDP, RISER SHOWS |
| | PLEASE SEE 240-3B FOR SIZING OF SEC`S |
| | FROM FPL. SHOWS ONLY, 4-500MCM`S IN |
| | 4-SETS.310-16/110-14 |
| | |
| | 12)NOTE: PLEASE INDICATE AND SHOW REQ`D |
| | GFI PROTECTION FOR HDP. 230-95/215-10 ET |
| | |
| | 13)NOTE: PLEASE CLARIFY/INDICATE METER |
| | TYPES FOR HOUSE AND FIRE PUMP? OF THE |
| | CT TYPE? |
| | |
| | 14)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROETECTED CIRCUITS ON EACH PANEL SCHED- |
| | -ULE PER 210-12 |
| | |
| | 15)NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | ED PER 210-8A-6THIS WOULD INCLUDE ANY |
| | ISLAND RECEPTS. |
| | |
| | 16)NOTE: PLEASE SEE PLANS AND UNITS, |
| | MISSING RECEPTS PER 210-52. 2',6',12' |
| | RULE. |
| | |
| | 17)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRLEATE W/ SUBMITTED PANEL |
| | SCHEDULES. |
| | |
| | 18)NOTE: PLEASE SEE V/33, APPEARS TO |
| | HAVE 2-WATER HEATERS AND 2-A/C UNITS? |
| | PLEASE CLARIFY. |
| | |
| | 19)NOTE: PLEASE SEE MISSING COUNTERSPACE |
| | RECEPTS PER 210-52-1 |
| | |
| | 20)NOTE: PLEASE CLARIFY GFI PROTECTION |
| | FOR WHIRLPOOL TUBS 680-70 |
| | |
| | 21)NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-52D/210-11C-3 |
| | MUST BE 20A/ #12AWG. |
| | |
| | 22)NOTE: PLEASE CLARIFY SQ FT SHOWN FOR |
| | UNIT D36, "L"UNITS? "L" UNITS ARE SHOWN |
| | MUCH LARGER ON SMAE SCLE THAN D36 , YET |
| | SQFT ON LOAD CALCS AND PANEL SCHEDULE |
| | DO NOT SEEM TO REFLECT THIS. |
| | PLEASE VERIFY OTHE UNITS ALSO. |
| | |
| | 23)NOTE: PLEASE VERIFY SQ FT ON OTHER |
| | UNITS ALSO. SOME OTHERS DO NOT SEEM TO |
| | SCALE OUT. |
| | |
| | 24)NOTE: PLEASE SEE OTHER UNITS FOR |
| | MISSING RECEPTS PER 210-52/210-52C-1 |
| | |
| | 25)NOTE: PLEASE SEE MISSING RECEPT W/IN |
| | 3' OF LAV IN "L" UNITS. 210-52D |
| | |
| | 26)NOTE: PLEASE NOTE: ALL SD`S TO BE A |
| | MIN OF 3' FROM BATHS AND KITCHENS. |
| | NFPA-72 8-1.4.2 |
| | |
| | 27)NOTE: PLEASE SEE MISSING RECEPT W/IN |
| | 3' OF LAV`S IN OTHER UNITS ALSO 210-52D |
| | |
| | 28)NOTE: PLEASE CLARIFY EGRESS LIGHTING |
| | CONTROL IN MULTI-LEVEL UNIT A/13. |
| | FOR STAIRWAY ,210-70 |
| | PLEASE ALSO SEE A17 |
| | |
| | 29)NOTE:PLEASE CLARIFY MEANS OF EGRESS |
| | LIGHTING/CONTROL OR AUTOMATIC MEANS |
| | FOR GRADE LEVEL UNITS W/ ACCESS TO |
| | STREET. |
| | |
| | 30)NOTE: PLEASE SHOW LIGHTING AND RECEPT |
| | -S SHOWN 2.9/2.10 ETC ON UNITS,, G-14, |
| | K-16,K18,K-20, L-22 ETC.OR NOTE |
| | LOCATION FO LIGHTING AND RECEPT. |
| | |
| | 31)NOTE: PLEASE SEEMISSING RECEPTS |
| | FOR 12" OF COUNTERSPACE,210-52C1 |
| | |
| | 32)NOTE: PLEASE SEE WHIRLPOOL TUB SHOWN |
| | IN MIDDLE OF MASTER BEDROOM FLOOR IN |
| | UNIT C/17, E 4.8 |
| | |
| | 33)NOTE: AS PER 210-52, RAIL AREA IN |
| | BEDROOMS ON MULTI-LEVEL UNITS ARE |
| | CONSIDERED WALL SPACE. RECEPT RE`D. |
| | |
| | 34)NOTE: PLEASE CLARFIY MEANS OF EGREES |
| | CONTROL COMING INTO S1(N) FROM HALL INTO |
| | LIVING ROOM.210-70 |
| | |
| | 35)NOTE: PLEASE CLARIFY METER CENTER "A" |
| | SHOWS 150A MAINS AND ONLY 7 V/33 UNITS? |
| | |
| | 36)NOTE: PLEASE SHOW SPECS ON PANEL |
| | SCHEDULES. FEEDERS ARE NOTED AS 125A AND |
| | 150ABUT PANELS DO NOT INDICATE SIZE |
| | ETC. |
| | |
| | 37)NOTE: PLEASE NOTE, POOL WILL BE REQ`D |
| | TO BE UNDER SEPARATE PERMIT FOR STRUC/ |
| | ELEC/PLUMB. PLEASE ALSO NOTE, A SEPARATE |
| | ELECTRCIAL WIRING DIAGRAM FOR PUMPS/ |
| | HEATERS AND EQUIPMENT WILL BE REQ`D TO |
| | BE SUBMITTED W/ POOL PERMIT. |
| | |
| | 38)NOTE:PLEASE NOTE, LIGHTNING PROTECT- |
| | -ION WILL BE REQ` TO BE UNDER SEPARATE |
| | PERMIT. |
| | |
| | 39)NOTE: PLEASE NOTE; COLOR CODING OF |
| | FEEDERS TO BE PER LOCAL AMENDMENTS. 215 |
| | 277/480V |
| | BROWN/ PURPLE /YELLOW |
| | 120/208V |
| | BLACK/RED/BLUE |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. PLEASE DO NOT HESITATE TO CALL |
| | AND EITHER SET UP A MEETING TO GO OVER |
| | PLANS/COMMENTS ON PHONE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |
| | 561-805-6717 |
| | [email protected] |
| | |
| | PLEASE SEE FIRE REVIEW COMMENTS THAT |
| | WILL HAVE AN AFFECT ON ELECTRICAL PLANS |
| | DUE TO THE REQUEST OF MORE EXIT/EM LTS. |