| 2003-04-16 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03031778 |
| | ADD: 610 CLEMATIS ST |
| | CONT: WHITING -TURNER CONTRACTING |
| | TEL: (954)776-0800 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ARCH: B & A BERMELLO.AJAMIL & |
| | PARTNERS INC |
| | TEL: (305)859-2050 |
| | FAX: (305)859-9638 |
| | |
| | ENG:DER DE LOS REYE ENGINEERING INC |
| | TEL: (305)665-2778 |
| | FAX: (305)665-2793 |
| | |
| | BUILDING PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) PROVIDE DOCUMENTATION OF UNITY OF |
| | TITLE, SECOND THAT THE CITY ABANDED THE |
| | ALLEY WAY. |
| | |
| | 3)FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | SRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL INSPEC |
| | TION PLAN PREPARED BY THE ENGINEER OF |
| | RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING AGEN- |
| | CY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESH- |
| | OLD BUILDING. THE PURPOSE OF THE SRUCTUR |
| | AL INSPECTION PLAN IS TO PROVIDE SPECIF- |
| | IC INSPECTION PROCEDURES AND SCHEDULES |
| | SO THAT THE BUILDING CAN BE ADEQUATELY |
| | INSPECTED FOR COMPLIANCE WITH THE |
| | PERMITTED DOCUMENTS. |
| | |
| | FOR THRESHOLD BUILDINGS FOR THE PER- |
| | MIT SET OF PLANS, PROVIDE (3) THREE COP- |
| | IES OF ALL DOCUMENTS, INCLUDING SHOP |
| | DRAWINGS, PRODUCT APPROVALS, LETTERS, |
| | ETC. EXCEPTION: THE STRUCTURAL CALCULA- |
| | TIONS (7 BOOKS). |
| | |
| | 4) PLANS INDICATE THAT THIS BUILDING |
| | IS PLANNED TO BE A CONDOMINIUM. BEFORE |
| | THE BUILDING WILL RECEIVE A CERTIFICATE |
| | OF OCCUPANCY THE DOCUMENT " DECLARATION |
| | OF CONDOMINIMUM" IS TO BE SUBMITTED TO |
| | THE STATE, APPROVED AND THEN RECORDED |
| | AT THE COUNTY CLERK OF THE COURT. THE |
| | CITY WILL NEED TO HAVE A RECORDED COPY |
| | FOR OUR RECORDS, ADDRESSING AND NOTIFICA |
| | TION OF THE PROPERTY APPRAISERS OFFICE. |
| | |
| | 5) AMENDMENTS TO APPENDIX F, FLORIDA |
| | BUILDING CODE, 2001 ED. LOCAL FIRE |
| | DISTRICT, SECTIONS 102- 105 SHALL APPLY |
| | TO THIS STRUCTURE. SEE ATTACHMENTS. |
| | |
| | 6) CHAPTER 13, FLORIDA ENERGY CODE, |
| | SECTION 400, ENERGY CALCULATIONS FOR THE |
| | WHOLE BUILDING. |
| | |
| | 7) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | PLEASE PROVIDE SOILS REPORT PREFORMED BY |
| | ARDAMAN & ASSOCIATES, GEOTECNICAL |
| | REPORT # 01-2233 BASED ON 10-01-02 |
| | INVESTIGATION. (VIBROFLOTATION). |
| | 3 SIGNED/ SEALED COPIES. |
| | |
| | 8) REQUIREMENTS FOR SPECIAL FOUNDATION |
| | PERMIT: |
| | A) THRESHOLD INSPECTOR TO BE SIGNED ON |
| | WITH DON NEELY THRESHOLD/ RESIDENT |
| | INSPECTOR PROGRAM COORDINATOR @ EXT. |
| | 6665. |
| | B) FILED SOILS REPORTS. |
| | C) PROVIDE THE DESIGN FOR SHEET PILE |
| | BY SPECILITY ENGINEER, TO BE REVIEWED |
| | BY & ACCEPTED BY THE ENGINEER OF RECORD |
| | ( HECTOR DE LOS REYES). |
| | D) COUNTY IMPACT FEES PAID FOR THE |
| | COMPLETE BUILDING. |
| | E) STATE RADON FEES TO BE PAID TO CITY. |
| | |
| | 104.4.5. SPECIAL FOUNDATION PERMIT |
| | WHEN APPLICATION FOR A PERMIT TO ERECT |
| | OR ENLARGE A BUILDING HAS BEEN FILED, & |
| | PENDING ISSURANCE OF SUCH PERMIT, THE |
| | BUILDING OFFICIAL MAY, AT HIS/ HER |
| | DISCRETION, ISSUE A SPECIAL PERMIT FOR |
| | THE FOUNDATION ONLY, UPON WRITTEN RE- |
| | QUEST OF THE OWNER AND CONTRACTOR. THE |
| | HOLDER OF SUCH A SPECIAL PERMIT IS PRO- |
| | CEEDING AT HIS OR HER OWN RISK AND WITH- |
| | OUT ASSURANCE THAT A PERMIT FOR THE |
| | REMAINDER OF THE WORK WILL BE GRANTED |
| | AND THAT CORRECTIONS WILL NOT BE RE- |
| | QUIRED IN ORDER TO MEET THE PROVISIONS |
| | OF THE TECHNICAL CODE. |
| | *****FAIR HOUSING ACT***** |
| | 9)THE PRIMARY ENTRY DOOR OF COVERED |
| | DWELLING UNITS IS PART OF PUBLIC AND |
| | COMMON USE SPACES, THEREFORE, IT MUST BE |
| | ON AN ACCESSIBLE ROUTE & BE ACCESSIBLE, |
| | I.E., MEET THE ANSI REQUIREMENTS OF |
| | 4.13 DOORS. |
| | SHEET A-3-5AB,5BC & 5DA UNITS @ ELE. |
| | 42', ENTRY VS, SECONDARY ENTRY DOORS, |
| | THE PLANS INDICATE THAT THE ENTRY (PRI- |
| | MARY) DOORS ARE TO THE EXTERIOR, THE |
| | PRIMARY DOORS ARE TO BE ON AN ACCESSIBLE |
| | ROUTE, THE COORIDOR ENTRY DOOR SINCE IT |
| | IS SERVED BY AN ELEVATOR. LEVER HANDLE |
| | OR OTHER EASY TO USE DOOR HARDWARWE, |
| | ANSI 4.13.9. |
| | |
| | 10) A-3.1AB/ A-3.1BC LOWER BASEMENTS, |
| | NOT ON A ACCESSIBLE ROUTE, PLANS DO NOT |
| | INDICATE SIGNAGE "NOT ACCESSIBLE ROUTE". |
| | |
| | 11) POOL, POOL DECK AND SURROUNDING |
| | AREAS ARE TO BE ACCESSIBLE. NO INFORMA- |
| | TION IS PROVIDED FOR THIS AREA. |
| | |
| | 12)FAIR HOUS REGUIREMENT 7.2 USEABLE |
| | BATHROOMS(I) NOTE: CABINETS UNDER LAVA- |
| | TORIES ARE ACCEPTABLE PROVIDED THE BATH- |
| | ROOM HAS SPACE TO ALLOW A PARALLEL |
| | APPROACH BY A PERSON IN A WHEELCHAIR; |
| | IF PARALLEL APPROACH IS NOT POSIBLE WITH |
| | IN THE SPACE, ANY CABINETS PROVIDED |
| | WOULD HAVE TO BE REMOVABLE TO AFFORD THE |
| | NECESSARY KNEE CLEARENCE FOR FORWARD |
| | APPROACH. |
| | |
| | 13) POOLS ARE TO HAVE AN EFFICTIVE |
| | BARRIER ( PUBLIC POOLS DOH RULE 64E-9 |
| | FL ADMINISTRATIVE CODE) INDICATE WHERE |
| | THIS WILL BE AN ACCESSIBILITY THROUGH |
| | THE ENCLOSURE? |
| | IF CONCIDERED A PRIVATE POOL SEE SEC- |
| | TION 424.2.17.(1) -(8). |
| | |
| | 14) SHEET A-3-5DA CORRIDOR 154 LEVEL 42 |
| | (NORTH) INDICATES THE USAGE OF RAMPS BUT |
| | NO ELEVATIONS ARE PROVIDED? |
| | *****GENERAL BUILDING COMMENTS****** |
| | 15) IT IS DIFFICULT TO DO PLAN REVIEWS |
| | WITHOUT A LEGEND INDICATING WHAT TYPE |
| | OF INFORMATION IS BEING RELAYED THE |
| | BOX WITH A NUMBERIN IT???????ALL PAGES! |
| | |
| | 16) FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 17)1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST. |
| | |
| | 18)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. MISSING REPORTS: |
| | A) FIXED WINDOWS INCLUDING STORE FRONT |
| | B) SINGLE HUNG WINDOWS |
| | C) MULLIONS VERTICAL & HORIZONTAL |
| | D) EXTERIOR GLAXED DOORS BOTH SWINGING |
| | AND SLIDING DOORS. |
| | E) SOLID EXTERIOR DOORS |
| | F) EXTERIOR DOORS W/ TRANSOMS (1 UNIT) |
| | G) OVERHEAD GARAGE DOOR |
| | H) LOUVERED VENTS |
| | I) ROOFING ASSEMBLIES:(II) ROOF TILE |
| | (III) FLAT ROOF W/ INSULATION |
| | |
| | COMMENTS TO BE CONTINUED ON THE NEXT |
| | PENTIMATION BUILDING REVIEW SESSION!!!! |