Plan Review Notes
Plan Review Notes For Permit 03031736
Permit Number 03031736
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-21 00:00:00BUILDING CHECKLIST:
 1-PROVIDE ENERGY CALCULATIONS AS REQ'D
 BY CHAPTER 13 FBC 2001.
 2-FLOOR NEEDS TO BE RAISED AT 4" ABOVE
 FINISH GRADEAS REQUIRED BY SECTION
 1804.1.7 CITY AMENDMENTS TO FBC 2001.
 3-SPECIFY SIZE AND TYPE OF WINDOWS TO
 CHECK FOR BEDROOM EGRESS REQUIREMENTS
 SEC. 1005.4 FBC 2001.
 4-NEED 1 1/2" WATER STOP RECESS AT
 MASONRY WALL. SEC. 2111.1.9 OF CITY
 AMENDMENTS TO FBC 2001.
 5-COMPLETE SPECIFICATIONS ON TYPICAL
 WALL SECTION. SPECIFY FURRING STRIPS
 FOR INSTALLATION OF DRYWALL AND
 INSULATION. SEC. 104.2.1.2 CITY AMEND-
 MENTS TO FBC 2001.
 6-CONSTRUCTION VALUE DECLARED IS TOO LOW
 NEED TO INCLUDE LABOR AND MATERIALS.
 REVISE AS REQUIRED.
 7-NEED STORM SHUTTERS PRODUCT APPROVAL
 AND INSTALLATION SCHEDULE.
 8-NEED RECORDED NOTICE OF COMMENCEMENT.
 9-AFTER CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS, TAKE THEM TO PALM BEACH
 COUNTY BLDG (SOUTHERN BOULEVARD AND
 AUSTRALIAN AVE) TO PAY IMPACT FEES AND
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.