| Plan Review Notes For Permit 03031677 |
| Permit Number |
03031677 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-06-11 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT ONLY ONE PANEL | | | SCHEDULE AND LOAD CALCULATIONS. | | | SOME ITEMS THAT WERE NOTES ON FIRST | | | REVIEW WERE ADDRESSED ON ORIGINAL SHEET | | | AND NOT THE SAME ON ATTACHED PANEL SCH.? | | | | | | 2)NOTE: KITCHEN COUNTERSPACE STILL | | | MISSING RECEPTS REQ`D PER 210-52C1 | | | PLEASE ALSO NOTE, NO HAND DRAWN PENCIL | | | CHANGES ARE PERMITTED UNLESS DRAWN IN, | | | IN INK AND SIGNED/DATED BY THE EGINEER | | | OF RECORD. | | | | | | 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED "CIRCUITS" ON PANEL SCHEDULE. | | | 210-12. PLANS SHOW NOTE THAT MENTIONS | | | ARC RECEPTS? PLEASE NOTE, AS OF TODAYS | | | DATE, ARC FAULT RECEPTS HAVE NOT YET | | | COME OUT. | | | | | | 4)NOTE: PLEASE SEE MISSING RECEPT PER | | | 210-52 BR#3 | | | | | | 5)NOTE: PLEASE SEE TWO DIFFERENT PANEL | | | SCHEDULES. ONE SHOWS MCB AND OTHER MLO? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|