| Notes |
| Date |
Text |
| 2003-03-31 00:00:00 | DENIED; | | | PAGE 2OF 10 PLUMBING RISER DIAGRAM DOES | | | NOT MATCH FLOOR PLAN. CABANA BATH AND | | | BAR SINK MISSING. 1/2 BATH LAV DOWN | | | STREAM OF W/C. MASTER BATH LAVS CANNOT | | | BE INSTALLED ON SAME STACK. KITCHEN SINK | | | SINK SHOULD HAVE A MECHANICAL VENT, NO | | | WALL FOR STACK. UTILITY SINK AND W/M ARE | | | ON DIFFERENT WALL. UP STAIR BATH NEED | | | TWO STACKS FOR LAVS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|