| Date |
Text |
| 2003-04-03 00:00:00 | ************ UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SEE MISSING SD ON LOWER |
| | LEVEL AT BOTTOM OF STAIRS. NFPA-72 |
| | 8-1.4.2 |
| | |
| | 2)NOTE: PLEASE CLARIFY/VERIFY KW RATING |
| | FOR TANKLESS WATER HEATERS SHOWN AT 800W |
| | `S. PLEASE NOTE 800W TLWH ARE NOT A |
| | TYP SIZE FOR A HOUSE THIS SIZE. |
| | PLEASE SUBMIT SPECS ON UNITS BEING |
| | INSTALLED AND REDO LOAD CALCULATIONS. |
| | |
| | 3)NOTE: PLEASE SEE PANEL SCHEDULE, |
| | MANY ITEMS ARE SHOWN AS 2-POLE AND ONLY |
| | TAKE ONE SPACE IN PANEL AND ARE LABELED |
| | FOR 1-POLE??33,34,35 ,,, |
| | |
| | 4)NOTE: PLEASE SEE LOAD CALCUALTIONS, |
| | LOAD FOR AHU/HEAT ONLY SHOWS ONE OF THE |
| | 10KW UNITS IN LOAD CALCS?? |
| | PLEASE ADJUST PER NEC 220 |
| | |
| | 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTED CIRCUITS ON PANEL SCHEDULE |
| | PER 210-12 |
| | |
| | 6)NOTE: PLEASE VERIFY LOCATION OF TKLWH |
| | ON SECOND FLOOR, BEHIND BEDROOM DOOR |
| | IN BEDROOM #4?? |
| | |
| | 7)NOTE: PLEASE SUBMIT AIC RATING FOR |
| | NEW SERVICE EQUIPMENT BEING INSTALLED. |
| | ALL MAINS/PANELS/BRKRS ARE TO BE RATED |
| | FOR THE AVAILABLE FAULT CURRENT. 110-9 |
| | 215-5 |
| | |
| | 8)NOTE: PLEASE SEE MISSING RECEPT FOR |
| | KITCHEN COUNTERSPACE. PLEASE SEE 210-52 |
| | C-1. 12" OF COUNTER/WALL SPACE. |
| | |
| | 9)NOTE: PLEASE SEE 210-52 FOR RECEPTS |
| | MISSING. 2',6',12' RULE. |
| | |
| | 10)NOTE: PLEASE CORRELATE PLAN AND PANEL |
| | SCHEDULE. PLAN SHOWS POOL PUMP AND |
| | IRRIGATION PUMP AT 220V AND PANEL SCH |
| | SHOWS 120V?? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |