| Plan Review Notes For Permit 03031594 |
| Permit Number |
03031594 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-21 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-RESUBMIT STORM SHUTTERS INFORMATION | | | WITH UPDATED SBCCI REPORT THAT MATCHES | | | ENGINEERED PLANS. CHECK DESIGN | | | PRESSURES SHOWN ON THE INSTALLATION | | | SCHEDULE AND MAX/MIN PANEL SPAN | | | ALLOWED ON DRAWINGS. SEC. 104.2.1.2 | | | CITY AMENDMENTS TO FBC 2001. | | | 2-RESUBMIT ENERGY CALCULATIONS WITH | | | ENGINEER'S ORIGINAL SIGNATURE & SEAL. | | | CHAPTER 471 FLORIDA STATUTES AND SEC. | | | 103.0 CHAPTER 13 FBC 2001. | | | 3-SPECIFY DETAIL AT TOP OF WOOD COLUMN. | | | BY STAIRS. SEE 2ND FLOOR FRAMING PLAN. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
|