| Plan Review Notes For Permit 03031456 |
| Permit Number |
03031456 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-02 00:00:00 | ************ NOTES/REDLINED*********** | | | | | | PLEASE SEE PLANS, THERE ARE MISSING ITEM | | | -S REDLINED. | | | | | | 1)NOTE: PLEASE MOVE SD INSIDE MASTER | | | BEDROOM.NFPA-72 8-1.4.2 | | | | | | 2)NOTE: PLEASE SEE 210-52C-1 FOR COUNTER | | | TOP OUTLET SPACING IN KITCHEN. MISSING | | | ONE. | | | | | | 3)NOTE: PLEASE SEE MISSING RECEPT PER | | | 210-52 W/IN 6' OF DOORWAY IN BREAKFAST | | | AREA. | | | 4)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN DISC | | | AND PANEL. SIZE PER 250-122 | | | | | | PLEASE REVISE PLANS BEFORE ROUGH. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | EELCTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|