| Plan Review Notes For Permit 03031449 |
| Permit Number |
03031449 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-02 00:00:00 | *************NOTES REDLINED ************ | | | | | | PLEASE NOTE, THE FOLLOWING ARE ITEMS | | | MISSING ON PLANS. | | | | | | 1)NOTE: PLEASE MOVE SD INTO MASTER | | | BEDROOM. NFPA-72 8-1.4.2 | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN DISCONNECT | | | TO PANEL. PER 250-122 | | | | | | 3)NOTE: PLEASE SEE MISSING COUNTERSPACE | | | RECEPT PER 210-52-C-1 | | | | | | 4)NOTE: PLEASE SEE MISSING RECEPT IN | | | BREAKFAST AREA W/IN 6' OF DOOR. 210-52 | | | | | | PLEASE REVISE AND SUBMIT FOR REVIEW | | | BEFORE ROUGH. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|