Plan Review Notes
Plan Review Notes For Permit 03031322
Permit Number 03031322
Review Stop B
Sequence Number 9
Notes
Date Text
2004-08-16 00:00:00****CORRECTIONS****
 RESPONSE TO PREVIOUS REVISION
 CCD #11, CCD #12, ASI #11 DATED 7/26/04
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE RESPONSE LETTER INDICATES THAT
 THE ATTACHED CCD#1 HAS THE DESIGN
 PRESSURES REQUESTED.CCD#11 CONTAINS
 THE NOA ONLY.YOU STATE THAT THE WIND
 PRESSURE FOR THE DOORS ARE AS NOTED FOR
 THE VESTIBULE WIND PRESSURE, S5.0.
 FBC 1606.1.7(5) REQUIRES THE DESIGN
 WIND PRESSURES TO BE ON THE PLAN.THE
 PLAN CURRENTLY HAS WIND PRESSURES FOR
 THE VESTIBULE ONLY.PLEASE INCLUDE
 THE DESIGN PRESSURE FOR THE DOOR AT
 THE DIETARY SERVICES ON THE PLAN AS THE
 RESPONSE LETTER IS NOT CONSIDERED A
 PART OF THE PLAN.
  
 2.)THE RESPONSE LETTER INDICATES AN
 OCCUPANCY OF I AND S RELATED TO THE FIRE
 RATED WALL.FBC TABLE 704.1 REQUIRES
 A 2 HR OCCUPANCY SEPARATION FOR BOTH
 INSTITUTIONAL AND STORAGE, LOW HAZARD
 S2.PLEASE PROVIDE A NEW FIRE RATED
 WALL DETAIL.THE DETAIL IS TO CONTAIN
 A TITLE BLOCK AND TO BE SEALED AS IT
 IS BEING SUBMITTED FOR PUBLIC RECORD
 FAC61G1-23.003, 004.
  
 3.)DOOR #2 IS REQUIRED TO BE A 1 1/2
 HR DOOR (IN A 2 HR WALL) FBC TABLE
 705.1.2.
  
 4.)IT APPEARS THAT SDAS3.G-1 AND
 SDAS4.G-1 ARE TO BE A PART OF THE
 REVISION PACKAGE.IF THIS IS THE CASE,
 PLEASE REMOVE THEM FROM THE "OLD SHEETS"
 AND COLLATE WITH THE REVIEW SHEETS.