| 2004-08-16 00:00:00 | ****CORRECTIONS**** |
| | RESPONSE TO PREVIOUS REVISION |
| | CCD #11, CCD #12, ASI #11 DATED 7/26/04 |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)THE RESPONSE LETTER INDICATES THAT |
| | THE ATTACHED CCD#1 HAS THE DESIGN |
| | PRESSURES REQUESTED.CCD#11 CONTAINS |
| | THE NOA ONLY.YOU STATE THAT THE WIND |
| | PRESSURE FOR THE DOORS ARE AS NOTED FOR |
| | THE VESTIBULE WIND PRESSURE, S5.0. |
| | FBC 1606.1.7(5) REQUIRES THE DESIGN |
| | WIND PRESSURES TO BE ON THE PLAN.THE |
| | PLAN CURRENTLY HAS WIND PRESSURES FOR |
| | THE VESTIBULE ONLY.PLEASE INCLUDE |
| | THE DESIGN PRESSURE FOR THE DOOR AT |
| | THE DIETARY SERVICES ON THE PLAN AS THE |
| | RESPONSE LETTER IS NOT CONSIDERED A |
| | PART OF THE PLAN. |
| | |
| | 2.)THE RESPONSE LETTER INDICATES AN |
| | OCCUPANCY OF I AND S RELATED TO THE FIRE |
| | RATED WALL.FBC TABLE 704.1 REQUIRES |
| | A 2 HR OCCUPANCY SEPARATION FOR BOTH |
| | INSTITUTIONAL AND STORAGE, LOW HAZARD |
| | S2.PLEASE PROVIDE A NEW FIRE RATED |
| | WALL DETAIL.THE DETAIL IS TO CONTAIN |
| | A TITLE BLOCK AND TO BE SEALED AS IT |
| | IS BEING SUBMITTED FOR PUBLIC RECORD |
| | FAC61G1-23.003, 004. |
| | |
| | 3.)DOOR #2 IS REQUIRED TO BE A 1 1/2 |
| | HR DOOR (IN A 2 HR WALL) FBC TABLE |
| | 705.1.2. |
| | |
| | 4.)IT APPEARS THAT SDAS3.G-1 AND |
| | SDAS4.G-1 ARE TO BE A PART OF THE |
| | REVISION PACKAGE.IF THIS IS THE CASE, |
| | PLEASE REMOVE THEM FROM THE "OLD SHEETS" |
| | AND COLLATE WITH THE REVIEW SHEETS. |