| Plan Review Notes For Permit 03031322 |
| Permit Number |
03031322 |
|
| Review Stop |
B |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2004-06-22 00:00:00 | ****CORRECTIONS**** | | | REVISION - SDAS3.G-1, SDA4.G-1, SDAS3G1 | | | DATED 6/8/04 | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)PROVIDE DESIGN PRESSURES FOR THE | | | EXTERIOR DOORS (NEW 6'0 DOUBLE DOORS | | | SHOWN ON SDA5.G-1). | | | | | | 2.)NOTE #7 ON SHEET SDA5.G-1 STATES | | | "UPGRADE THE FIRE RATING OF THE EXISTING | | | WALL".PLEASE PROVIDE A DETAIL, | | | INCLUDING UL ASSEMBLY # OR CALCULATED | | | FIRE RESISTANCE.DECLARE AN OCCUPANCY | | | ON EITHER SIDE OF THE WALL. | | | | | | 3.)DOOR #2 IS TO COMPLY WITH OPENING | | | PROTECTIVE REQUIREMENT, IF ANY, AS PER | | | FBC TABLE 705.1.2. | | | | | | 4.)HANDRAILS ARE REQUIRED ON BOTH | | | SIDES OF THE RAMP, FBC1013.7.EDGE | | | PROTECTION REQUIRED, FBC1013.8. | | | | | | 5.)HANDRAIL IS TO COMPLY WITH FBC | | | 11-4.8.5(2) (EXTEND 18" PARALLEL AT | | | TOP AND BOTTOM). | | | | | | 6.)SDAS3.G-1 SHOWS NEW OXYGEN TANKS, | | | SDA5.G-1 SHOWS THEM AS EXISTING. | | | ADDRESS. | | | | | | 7.)PROVIDE A VALUE FOR THE ADDITIONAL | | | WORK. |
|