| Plan Review Notes For Permit 03031322 |
| Permit Number |
03031322 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-11 00:00:00 | PLAN REVIEW ONLY NOT A PERMIT | | | APPLICATION. | | | | | | THE NEW STEPS SHOWN IN SECTION D/A10.G | | | REQUIRE HANDRAILS ON EACH SIDE.SEE | | | FBC 1007.5.2. | | | | | | ARCHITECTURAL TRIM DEPICTED VARIOUSLY ON | | | THE PLANS AS "EIFS BANDING" OR "EIFS | | | BRACKETS" MUST COMPLY WITH FBC 1404.1.1. | | | | | | THE EIFS MUST COMPLY WITH FBC 2603.6 AND | | | THE MANUFACTURER'S SPECIFIC SYSTEM AS | | | WWELL AS THE EVALUATION REPORT FOR THAT | | | SYSTEM FROM A RECOGNIZED EVALUATION | | | SERVICE. | | | | | | THE ENTRANCE CANOPY DOES NOT DEFINE AS A | | | CANOPY IN ACCORDANCE WITH FBC 3106 | | | SINCE IT IS LARGER THAN FIFTEEN FEET, | | | THERE FOR IT IS PART OF THE BUILDING | | | AND MUST COMPLY WITH TYPE II | | | CONSTRUCTION. |
|