| Plan Review Notes For Permit 03031318 |
| Permit Number |
03031318 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-06-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | | | | 1) SHT MEP-1 SANITARY RISER DIAGRAM & | | | WATER RISER DIAGRAM. FINAL PLAN REVIEW | | | NOTE FOR PLUMBING STATES THAT SANT. AND | | | WATER RISERS SHALL BE SUBMITTED AT TIME | | | OF PLUMBING PERMIT APPLICATION. ALL | | | RISER DIAGRAM SHALL SHOW ALL PIPE SIZES, | | | AND VENTING. SECTION 1-4.2.1 | | | | | | 2) ONLY FIXTURES FROM THE BATHROOM GROUP | | | SHALL DRAIN INTO THE WET VENT FOR THE | | | BATHROOM FIXTURES. ALL OTHER FIXTURES | | | SHALL TIE IN DOWNSTREAM OF THE WET VENT. | | | SECTION 909.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|