Plan Review Notes
Plan Review Notes For Permit 03031318
Permit Number 03031318
Review Stop P
Sequence Number 4
Notes
Date Text
2003-06-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
  
 1) SHT MEP-1 SANITARY RISER DIAGRAM &
 WATER RISER DIAGRAM. FINAL PLAN REVIEW
 NOTE FOR PLUMBING STATES THAT SANT. AND
 WATER RISERS SHALL BE SUBMITTED AT TIME
 OF PLUMBING PERMIT APPLICATION. ALL
 RISER DIAGRAM SHALL SHOW ALL PIPE SIZES,
 AND VENTING. SECTION 1-4.2.1
  
 2) ONLY FIXTURES FROM THE BATHROOM GROUP
 SHALL DRAIN INTO THE WET VENT FOR THE
 BATHROOM FIXTURES. ALL OTHER FIXTURES
 SHALL TIE IN DOWNSTREAM OF THE WET VENT.
 SECTION 909.1
  