Plan Review Notes
Plan Review Notes For Permit 03031318
Permit Number 03031318
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2003-05-02 00:00:001) PLANS DO NOT INDICATE LOCATIONS
 OF ILLUMINATED EXIT SIGNS.
  
 2) PLANS AGAIN DO NOT INDICATE IF THE
 BUILDING IS FIRE SPRINKLER PROTECTED.
  
 3) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION PROVIDED FOR WALLS AND
 CEILINGS.
  
 4) THE ONE HOUR WALL THAT IS BEING
 PROPOSED SHALL BE AT LEAST TWO HOUR
 FIRE RATED WITH ONE AND HALF HOUR
 OPENING PROTECTIVES. TIRE STORAGE AND
 RETAIL AREA.
  
 5) NO EXPLANATION ON HOW TIRES WILL
 BE STORED.
  
 6) PLEASE SHOW DEMISING WALLS AND
 THEIR RESPECTIVE FIRE RATINGS.
  
 7) NO OCCUPANT LOAD TOTALS PROVIDED.
  
 8) NO DETAILS ON VEHICLE STORAGE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910