| Plan Review Notes For Permit 03031318 |
| Permit Number |
03031318 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-02 00:00:00 | 1) PLANS DO NOT INDICATE LOCATIONS | | | OF ILLUMINATED EXIT SIGNS. | | | | | | 2) PLANS AGAIN DO NOT INDICATE IF THE | | | BUILDING IS FIRE SPRINKLER PROTECTED. | | | | | | 3) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED FOR WALLS AND | | | CEILINGS. | | | | | | 4) THE ONE HOUR WALL THAT IS BEING | | | PROPOSED SHALL BE AT LEAST TWO HOUR | | | FIRE RATED WITH ONE AND HALF HOUR | | | OPENING PROTECTIVES. TIRE STORAGE AND | | | RETAIL AREA. | | | | | | 5) NO EXPLANATION ON HOW TIRES WILL | | | BE STORED. | | | | | | 6) PLEASE SHOW DEMISING WALLS AND | | | THEIR RESPECTIVE FIRE RATINGS. | | | | | | 7) NO OCCUPANT LOAD TOTALS PROVIDED. | | | | | | 8) NO DETAILS ON VEHICLE STORAGE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|