Plan Review Notes
Plan Review Notes For Permit 03031318
Permit Number 03031318
Review Stop B
Sequence Number 2
Notes
Date Text
2003-05-01 00:00:00PLEASE PROVIDE SPECIFIC CONSTRUCTION
 DETAILS AND ENGINEERING FOR THE
 INSTALLATION OF THE NEW DOORS TO BE CUT
 INTO THE WALL SHOWN AS 105B 105C AND
 E108. FBC 104.2.
  
 SHOW THE WIND DESIGN PRESSURES FOR THE
 OPENINGS IN THE EXTERIOR WALL SEE FBC
 1606.1.7.
  
 THE STORAGE AREA REQUIRES A MINIMUM TWO
 HOUR FIRE RATED SEPARATION.SEE FBC
 7041.1.
  
 THE SERVICE AREA REQUIRES A ONE HOUR
 FIRE RATED SEPARATION, (GROUP B SIM
 404.5) FROM THE MERCANTILE USE.
  
 ALL OF THE FIRE RATED WALLS REQUIRE
 FIRE RATED OPENING PROTECTION.FBC
 705.1.2.
  
 EGRESS IS NOT ALLOWED THROUGH THE
 STORAGE ROOM.SEE FBC1001.1.3.
  
 SHEET A3, WHAT IS THE NEW CEILING THAT
 IS TO MATCH THE EXISTING CEILING HEIGHT?
  
 SHEET A4, SHOW SPECIFIC CONSTRUCTION
 DETAILS AND FASTENINGS FOR THE BRACING
 OF THE PARTITIONS NOTED UNDER PARTITION
 NOTES.SEE FBC 104.2.