| Plan Review Notes For Permit 03031318 |
| Permit Number |
03031318 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-01 00:00:00 | PLEASE PROVIDE SPECIFIC CONSTRUCTION | | | DETAILS AND ENGINEERING FOR THE | | | INSTALLATION OF THE NEW DOORS TO BE CUT | | | INTO THE WALL SHOWN AS 105B 105C AND | | | E108. FBC 104.2. | | | | | | SHOW THE WIND DESIGN PRESSURES FOR THE | | | OPENINGS IN THE EXTERIOR WALL SEE FBC | | | 1606.1.7. | | | | | | THE STORAGE AREA REQUIRES A MINIMUM TWO | | | HOUR FIRE RATED SEPARATION.SEE FBC | | | 7041.1. | | | | | | THE SERVICE AREA REQUIRES A ONE HOUR | | | FIRE RATED SEPARATION, (GROUP B SIM | | | 404.5) FROM THE MERCANTILE USE. | | | | | | ALL OF THE FIRE RATED WALLS REQUIRE | | | FIRE RATED OPENING PROTECTION.FBC | | | 705.1.2. | | | | | | EGRESS IS NOT ALLOWED THROUGH THE | | | STORAGE ROOM.SEE FBC1001.1.3. | | | | | | SHEET A3, WHAT IS THE NEW CEILING THAT | | | IS TO MATCH THE EXISTING CEILING HEIGHT? | | | | | | SHEET A4, SHOW SPECIFIC CONSTRUCTION | | | DETAILS AND FASTENINGS FOR THE BRACING | | | OF THE PARTITIONS NOTED UNDER PARTITION | | | NOTES.SEE FBC 104.2. |
|