| Plan Review Notes For Permit 03031318 |
| Permit Number |
03031318 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-26 00:00:00 | ********** UNSAT **************** | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH SUBMITTED PANEL | | | SCHEDULE. | | | | | | 2)NOTE: PLEASE SEE PLANS, PANEL SCHEDULE | | | SHOWS "SHOW WINDOW" AND RECETPS ARE NOT | | | SHOWN ON PLANS? | | | 210-62 | | | | | | 3)NOTE: PLEASE CLARIFY NEW OR EXSITNG | | | SIGN CIRCUIT PER 600-5. | | | | | | 4)NOTE: PLEASE SHOW ALL CONTINOUS LOADS | | | AT 125%. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|