| Plan Review Notes For Permit 03031318 |
| Permit Number |
03031318 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-08 00:00:00 | | | | THE PLANS DO NOT HAVE ENOUGH | | | INFORMATION SEE FBC 104.2.1. | | | | | | IT APPEARS NEW DOORS WILL BE CUT INTO | | | THE SERVICE AREA.SHOW A DETAIL. | | | | | | SHOW A CONSTRUCTION DETAIL FOR THE | | | PARTITIONS INCLUDING FIRE DESIGN NUMBER | | | WHERE APPLICABLE. | | | | | | PROVIDE A DOOR AND WINDOW SCHEDULE. | | | | | | SHOW OR NOTE THE CEILING EXISTING OR | | | PROPOSED. | | | | | | PROVIDE A FIRE RATED MIXED OCCUPANCY | | | SEPARATION IN ACCORDANCE WITH FBC 704.1. | | | 1 FOR MERCANTILE AND STORAGE. | | | | | | SHOW THE FIRE RATED SEPARATION IF THIS | | | IS A MULTIPLE TENANT BUILDING. | | | | | | SHEET A1, WHAT DOES THE DOTTED LINE | | | REPRESENT BETWEEN THE RETAIL DISPLAY | | | AND THE WHEEL TIRE STORAGE? | | | | | | SHOW THE HANDICAP ACCESSIBILITY IN | | | ACCORDANCE WITH FBC 11-4.1.6 (2) | | | | | | SHOW THE AIR CONDITIONING WORK WHERE | | | APPLICABLE. |
|