Plan Review Notes
Plan Review Notes For Permit 03031261
Permit Number 03031261
Review Stop P
Sequence Number 1
Notes
Date Text
2003-03-24 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92, AND NSPI-5. (ADD TO
 NOTES)
 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 3) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 4) INDICATE WHETHER OR NOT THERE IS A
 POOL HEATER. (NOT SHOWN ON POOL SPECS.)
 5) POOL PIPING SCHEMATIC SHOWS SPA DRAIN
 BUT NO SPA SHOWN ON POOL LAYOUT. PLEASE
 SUBMIT SCHEMATIC THAT REFLECTS POOL AS
 IT WILL BE BUILT.
 6) AN ENGINEERS TITLE BLOCK SHALL HAVE
 HIS NUMBER INCLUDED. 61G15-23.002(2)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377