2003-04-03 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY CONDUCTORS
 ON SERVICE? SHOWS 3/0` TO 100A AND 50A
 PANEL? PLEASE CLARIFY HOW 3/0'S WILL FIT
 IN LUGS?
 PLAN ALSO SHOWS 350 MCM FOR 150A SERVICE
 ?
 PLEASE CALFIY THE ABOVE.
  
 2)NOTE: PLEASE ALSO SEE 250-66 FOR
 SIZING OF GROUNDING ELECTRODE SYSTEM.
 PER 350MCM'S?
  
 3)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 SHOWING ALL NEW AND EXSITING.215-5
  
 4)NOTE: PLEASE SHOW ALL KITCHEN COUNTER-
 -SPACE OUTLETS AS GFI/ GFI PROTECTED.
 210-8-A-6
  
 5)NOTE: PLEASE SEE PLANS,SOME AREAS ARE
 DARK AND CLEARLY VISABLE. PLEASE REPRINT
 FOR CLARITY. 104.2
  
 6)NOTE: PLEASE SHOW ALL OUTSIDE RECEPTS
 AS GFI.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  