| 2003-04-03 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE CLARIFY CONDUCTORS | | | ON SERVICE? SHOWS 3/0` TO 100A AND 50A | | | PANEL? PLEASE CLARIFY HOW 3/0'S WILL FIT | | | IN LUGS? | | | PLAN ALSO SHOWS 350 MCM FOR 150A SERVICE | | | ? | | | PLEASE CALFIY THE ABOVE. | | | | | | 2)NOTE: PLEASE ALSO SEE 250-66 FOR | | | SIZING OF GROUNDING ELECTRODE SYSTEM. | | | PER 350MCM'S? | | | | | | 3)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS | | | SHOWING ALL NEW AND EXSITING.215-5 | | | | | | 4)NOTE: PLEASE SHOW ALL KITCHEN COUNTER- | | | -SPACE OUTLETS AS GFI/ GFI PROTECTED. | | | 210-8-A-6 | | | | | | 5)NOTE: PLEASE SEE PLANS,SOME AREAS ARE | | | DARK AND CLEARLY VISABLE. PLEASE REPRINT | | | FOR CLARITY. 104.2 | | | | | | 6)NOTE: PLEASE SHOW ALL OUTSIDE RECEPTS | | | AS GFI. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|