| Plan Review Notes For Permit 03031228 |
| Permit Number |
03031228 |
|
| Review Stop |
M |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2004-05-28 00:00:00 | PROVISO: | | | 1.ADDITIONAL PERMITS REQUIRED FOR HOOD | | | AND FIRE SUPPRESSION PER 2001 FBC(M) | | | 506.1. | | | | | | 2.PLEASE NOTE, DUCTS PENETRATING A | | | WALL WITH A FIRE RESISTANCE RATING SHALL | | | HAVE A FIRE DAMPER OR COMPLY WITH THE | | | EXCEPTION PER 2001 FBC(M) 607.1.2 AND | | | 607.1.3. | | | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS PER NFPA 90A | | | 6.4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|