| Plan Review Notes For Permit 03031228 |
| Permit Number |
03031228 |
|
| Review Stop |
M |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2004-05-04 00:00:00 | DENIED: | | | FUTURE PLAN SUBMITTALS SHALL BE LISTED | | | AS REVISIONS & NOT SUBMITTALS. | | | | | | 1.REVISION SUBMITTED IS NOT DONE BY | | | THE ENGINEER OF RECORD. PLEASE PROVIDE | | | LETTER BY THE ENGINEER OF RECORD OR | | | OWNER INIDCATING THE RELEASE OF SAID | | | PLANS. | | | | | | 2.DUCT SMOKE DETECTORS REQUIRED IN | | | UNITS THAT HAVE THE DESIGN CAPACITY | | | GREATER THAN 2,000 CFM.PLEASE | | | INDICATE DUCT SMOKE DETECTORS ON THE | | | PLAN. | | | | | | 3.ORIGINAL PLANS SUBMITTED INDICATE | | | CORRIDORS HAVING A 1 HR FIRE RESISTANCE | | | RATING.NO FIRE DAMPERS ARE INDICATED | | | ON THE NEW/REVISED PLAN.PLEASE CLARIFY | | | | | | 4.NEW ENGINEER SHALL COMPLY WITH FS | | | 471.025 & THE FAC 61G15-23.002.PROVIDE | | | TITLE BLOCK, INDIACATE LICENSE NUMBER AS | | | WELL AS DATE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|