2004-05-04 00:00:00DENIED:
 FUTURE PLAN SUBMITTALS SHALL BE LISTED
 AS REVISIONS & NOT SUBMITTALS.
  
 1.REVISION SUBMITTED IS NOT DONE BY
 THE ENGINEER OF RECORD. PLEASE PROVIDE
 LETTER BY THE ENGINEER OF RECORD OR
 OWNER INIDCATING THE RELEASE OF SAID
 PLANS.
  
 2.DUCT SMOKE DETECTORS REQUIRED IN
 UNITS THAT HAVE THE DESIGN CAPACITY
 GREATER THAN 2,000 CFM.PLEASE
 INDICATE DUCT SMOKE DETECTORS ON THE
 PLAN.
  
 3.ORIGINAL PLANS SUBMITTED INDICATE
 CORRIDORS HAVING A 1 HR FIRE RESISTANCE
 RATING.NO FIRE DAMPERS ARE INDICATED
 ON THE NEW/REVISED PLAN.PLEASE CLARIFY
  
 4.NEW ENGINEER SHALL COMPLY WITH FS
 471.025 & THE FAC 61G15-23.002.PROVIDE
 TITLE BLOCK, INDIACATE LICENSE NUMBER AS
 WELL AS DATE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.