 BUILDING PLAN REVIEW
 PERMIT: 03031228
 ADD: 4011 NORTH SHORE DRIVE
 CONT: DON CLAY
 TEL: (561)683-0609
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 2) REQUIRED CORRECTION- TITLE SHEET,
 NOT THE 2002 FLORIDA BUILDING CODE.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) EXT. METAL DOOR W/ 1/2 LIGHT (D-1)
 B) ROOF SHINGLES
  
 4) COMPONENTS & CLADDING SHEET A-23,
 THE WIND PRESSURES GIVEN ARE LOW,THE PRE
 SSURES TAKEN FROM TABLE 1606.2B ARE
 GIVEN WITHOUT ANY IMPORTANCE FACTOR
 INCREASES. THIS BUILDING IS TO BE DESIGN
 ED AT A IMPORTANCE FACTOR OF 1.15, ALSO
 THE MEAN ROOF HEIGHT IS APPROX 21.25'.
 WHICH ALSO INCREASES PRESSURES.
  
 5) NEW TO THE 2001 FLORIDA BUILDING CODE
 2117.1.2 CATHEDRAL END WALLS, AS PER
 FROM THE BUILDING OFFICIAL, THE PLANS
 SHALL COMPLY WITH THIS CODE SECTION AT
 TIME OF PERMITTING. THE CONTRACTOR MAY
 SUBMIT A REVISION UNDER ALTERNATE MATERI
 ALS AND METHODS, A PEER REVIEW WILL BE
 PREFORMED ,WITH AN INDEPENDENT ENGINEER
 OF THE CITY'S CHOICE AT THE COST TO THE
 PERMIT HOLDER.
  
 6) TRUSS I-JOIST ITEM (27) FROM SECOND
 PLAN REVIEW (A,B,D,E,&F HAVE NOT BEEN
 ADDRESSED.
 A) MISSING THE MANUFACTURERS SPEC &
 ROOF SPAN CHART?
 THE DESIGNER IS SPECING A 11 7/8"
 TRUSS- JOIST, NO MANUFACTURER SPECED,
 IF TRUSS-JOIST MC MAC MILLIAN IS THE
 JOIST TO BE SPECED, A RESIDENTIAL OR COM
 MERCIAL JOIST? WHAT SERIES OF JOIST,
 11 7/8" TJI 15 DF/SP,25DF/SP,35P,35P,
 40P OR 40C?????????????????????????
 B) PROVIDE CURRENT 2003 MANUFACTURERS
 INFORMATION, IS THIS A FACE MOUNT OR TOP
 MOUNT UNIT? USING THE 2 SIMPSON HGA10
 CLIPS A TOTAL COMBINED RESISTANCE IS
 870 LBS., ONLY THE BOTTOM FASTENER HOLES
 WILL CATCH THE BOTTOM RAIL OF THE I
 JOIST, AGAIN NO MENTION OF WEB STIFFEN-
 ERS TO INDICATE HOW TO TRANSFER LOADS.
 IN THIS CASE ONLY 1/2 THE LOAD OR 435
 LBS CAN BE USED.
 DEPENDING ON THE WIND ZONE LOCATION
 WORST CASE ZONE#3,21' SPAN@(-37.3X1.15)=
 -42.8PSF UPLIFTX42SQ FT(TRIBUTARY AREA)=
 1797/2=898.8 UPLIFT PER END.
 D) ARE WEB STIFFENERS REQUIRED? AT WHAT
 SPACING WILL THE BRIDING BE REQUIRED?
 E)COMMENT OK
 F) OUTLOOKERS NOW HAVE WEB STIFNERS BUT
 NO DETAIL FROM THE MANUFACTURER INDICATI
 NG THAT THEY ARE TO BE FULL HEIGHT, ON
 ONE SIDE ONLY ?
  
 7) THE MICRO-LAMB BEAM DETAIL SHEET IS
 NOT A ENGINEERED SHEET, THE SECOND ISSUE
 THE DESIGN WAS UNDER THE 1997 SBC @
 110 MPH. THE FLORIDA CODE IS 140 MPH,
 THIS DESIGN WILL NEED TO BE UPGRADED TO
 THE PRESENT DAY CODE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026