Text |
| 2003-07-28 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 AMENDMENTS, CHAPTER |
| | ONE, ADMINISTRATION |
| | CODE. |
| | |
| | 1) FROM PREVIOUS REVIEW: COMMENT NUMBERS |
| | TO STAY THE SAME FOR CLAIRTY. |
| | (2) SUBMIT CALCULATIONS FOR MINIMUM FIX- |
| | TURES. NO INFORMATION IS GIVEN FOR THE |
| | GYMNASIUM AREA. WHERE ARE THE FACILITIES |
| | FOR THE GYM? WILL THE PATRONS BE ABLE TO |
| | USE THE FACILITIES IN THE SCHOOL AREA? |
| | POTTY PARITY PER SECTION 403.1.1 INDICA- |
| | TES THAT RESTROOM WHICH ARE OPEN TO THE |
| | PUBLIC MUST HAVE A RATIO OF 3 TO 2 WATER |
| | CLOSETS PROVIDED FOR WOMEN AS THE COM- |
| | BINED TOTAL OF WATER CLOSETS AND URNALS |
| | PROVIDED FOR MEN. |
| | 3) CALCULATIONS FOR PRIMARY AND SECOND- |
| | ARY ROOF DRAINS. ROOF AREAS "I" & "J" |
| | DO NOT SHOW THE ROOF AREA OF THE GYM |
| | THAT DRAINS ONTO THESE AREAS. ALSO NO |
| | MENTION OF VERTICAL WALLS IS SHOWN IN |
| | CALCULATIONS PROVIDED FOR ANY AREAS. |
| | SECTIONS 1106 & 1107 AND ALL SUBSECTIONS |
| | *COVER SHEET INDICATES 31 3" ROOF DRAINS |
| | BUT THERE ARE ONLY 26 3" ROOF DRAINS AND |
| | 6 2" ROOF DRAINS. PLEASE CLAIRFY. |
| | 4) PLEASE SUBMIT A DETAIL FOR THE SCUPP- |
| | ERS. SHOW HEIGHT AND WIDTH FOR OPENING |
| | AND INDICATE HEIGHT OFF ROOF TO FLOW |
| | LINE PER SECTION 1511.6.4.3 OF THE BLDG. |
| | CODE. |
| | 6) PLEASE PROVIDE A DETAIL FOR EACH |
| | TOILET ROOM. SHOW CLEAR FLOOR SPACE, |
| | TURNING CIRCLE 11-4.16.2, HEIGHT 4.16.3, |
| | GRAB BARS 4.16.4, FLUSH CONTROLS 4.16.5. |
| | SHOW CLEAR FLOOR SPACE 11-4.19.3, HEIGHT |
| | & CLEARANCES 4.19.2, EXPOSED PIPES AND |
| | SURFACES 4.19.4, AND FAUCETS 4.19.5 |
| | 7) DETAILS FOR TOILET ROOM BETWEEN CLASS |
| | ROOMS 1 & 2, AND 12 & 13 REQUIRED. SEE |
| | ABOVE COMMENT. |
| | 8) YOU MUST COMPLETE A WAIVER FOR THE |
| | USE OF CHILDREN'S FIXTURES IN THE SCHOOL |
| | THE ACCESSIBILITY STANDARD IS ONLY A |
| | GUIDLINE AND HAS NOT BEEN ADOPTED BY THE |
| | DEPT. OF JUSTICE. THE WAIVER SHALL BE |
| | SUBMITTED TO DTATE OF FLA. DEPT. OF COMM |
| | AFFAIRS. PLEASE SUBMIT CUT SHEETS FOR |
| | CHILDRENS FIXTURES. |
| | 9) SHT P-1 PLEASE PROVIDE DETAILS FOR |
| | TEACHERS LOUNGE SINK. SHOW COMPLIANCE |
| | WITH SECTION 11-4.24 AND ALL SUBSECTIONS |
| | 13) TOILET ROOM FOR PRESIDENT SHALL BE |
| | ADAPTABLE - DETAILS REQUIRED - CLEAR |
| | FLOOR SPACE, TURNING CIRCLE, AND SHOW |
| | BACKING FOR GRAB BARS AND INDICATE THE |
| | HEIGHT AND WIDTH OF BACKING. 11-4.22 |
| | A) NEW COMMENT... PLANS INDICATE 1/8" |
| | PER FOOT ON SHEET A-1 BUT MEASURMENTS DO |
| | NOT REFLECT THIS SCALE. PLEASE CLAIRFY |
| | B) ALL RED LINE CORRECTIONS SHALL BE IN- |
| | ITALED AND DATED BY ARCHITECT/ENGINEER |
| | OF RECORD. |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |