Plan Review Notes
Plan Review Notes For Permit 03031228
Permit Number 03031228
Review Stop P
Sequence Number 3
Notes
Date Text
2003-07-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMINISTRATION
 CODE.
  
 1) FROM PREVIOUS REVIEW: COMMENT NUMBERS
 TO STAY THE SAME FOR CLAIRTY.
 (2) SUBMIT CALCULATIONS FOR MINIMUM FIX-
 TURES. NO INFORMATION IS GIVEN FOR THE
 GYMNASIUM AREA. WHERE ARE THE FACILITIES
 FOR THE GYM? WILL THE PATRONS BE ABLE TO
 USE THE FACILITIES IN THE SCHOOL AREA?
 POTTY PARITY PER SECTION 403.1.1 INDICA-
 TES THAT RESTROOM WHICH ARE OPEN TO THE
 PUBLIC MUST HAVE A RATIO OF 3 TO 2 WATER
 CLOSETS PROVIDED FOR WOMEN AS THE COM-
 BINED TOTAL OF WATER CLOSETS AND URNALS
 PROVIDED FOR MEN.
 3) CALCULATIONS FOR PRIMARY AND SECOND-
 ARY ROOF DRAINS. ROOF AREAS "I" & "J"
 DO NOT SHOW THE ROOF AREA OF THE GYM
 THAT DRAINS ONTO THESE AREAS. ALSO NO
 MENTION OF VERTICAL WALLS IS SHOWN IN
 CALCULATIONS PROVIDED FOR ANY AREAS.
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 *COVER SHEET INDICATES 31 3" ROOF DRAINS
 BUT THERE ARE ONLY 26 3" ROOF DRAINS AND
 6 2" ROOF DRAINS. PLEASE CLAIRFY.
 4) PLEASE SUBMIT A DETAIL FOR THE SCUPP-
 ERS. SHOW HEIGHT AND WIDTH FOR OPENING
 AND INDICATE HEIGHT OFF ROOF TO FLOW
 LINE PER SECTION 1511.6.4.3 OF THE BLDG.
 CODE.
 6) PLEASE PROVIDE A DETAIL FOR EACH
 TOILET ROOM. SHOW CLEAR FLOOR SPACE,
 TURNING CIRCLE 11-4.16.2, HEIGHT 4.16.3,
 GRAB BARS 4.16.4, FLUSH CONTROLS 4.16.5.
 SHOW CLEAR FLOOR SPACE 11-4.19.3, HEIGHT
 & CLEARANCES 4.19.2, EXPOSED PIPES AND
 SURFACES 4.19.4, AND FAUCETS 4.19.5
 7) DETAILS FOR TOILET ROOM BETWEEN CLASS
 ROOMS 1 & 2, AND 12 & 13 REQUIRED. SEE
 ABOVE COMMENT.
 8) YOU MUST COMPLETE A WAIVER FOR THE
 USE OF CHILDREN'S FIXTURES IN THE SCHOOL
 THE ACCESSIBILITY STANDARD IS ONLY A
 GUIDLINE AND HAS NOT BEEN ADOPTED BY THE
 DEPT. OF JUSTICE. THE WAIVER SHALL BE
 SUBMITTED TO DTATE OF FLA. DEPT. OF COMM
 AFFAIRS. PLEASE SUBMIT CUT SHEETS FOR
 CHILDRENS FIXTURES.
 9) SHT P-1 PLEASE PROVIDE DETAILS FOR
 TEACHERS LOUNGE SINK. SHOW COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS
 13) TOILET ROOM FOR PRESIDENT SHALL BE
 ADAPTABLE - DETAILS REQUIRED - CLEAR
 FLOOR SPACE, TURNING CIRCLE, AND SHOW
 BACKING FOR GRAB BARS AND INDICATE THE
 HEIGHT AND WIDTH OF BACKING. 11-4.22
 A) NEW COMMENT... PLANS INDICATE 1/8"
 PER FOOT ON SHEET A-1 BUT MEASURMENTS DO
 NOT REFLECT THIS SCALE. PLEASE CLAIRFY
 B) ALL RED LINE CORRECTIONS SHALL BE IN-
 ITALED AND DATED BY ARCHITECT/ENGINEER
 OF RECORD.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]