Plan Review Notes
Plan Review Notes For Permit 03031228
Permit Number 03031228
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2003-08-14 00:00:001) A 15 FOOT OPENING IS SHOWN ON
 NORTHSHORE DRIVE. A 20 FOOT OPENING
 IS REQUIRED FOR FIRE AND PARAMEDICAL
 EQUIPMENT.
  
 2) POST INDICATOR VALVES ARE REQUIRED.
  
 3) ELECTRONIC SWITCHES ARE REQUIRED
 ON THE BACKFLOW DEVICE.
  
 4) SHEET S-7 FIRE HYDRANT LOCATION
 IS IN A DIFFERENT LOCATION THAN
 PREVIOUS DRAWING.
  
 5) A KNOX-BOX WILL BE REQUIRED.
  
 6) SHEET A-2 NEAR CLASSROOM # 7 IS
 MISSING AN EXTERIOR DOOR.
  
 7) IS THE FDC PLANNED TO BE INSTALLED
 NEAR THE FENCED PLAY AREA.
  
 8) PLEASE INDICATE LOCATION OF MAIN
 ENTRY AND EGRESS DOORS. PLEASE
 DEMONSTRATE THAT 50 PERCENT OF THE
 TOTAL OCCUPANT LOAD CAN EXIT VIA
 THE MAIN ENTRY OR EGRESS DOORS.
  
 9) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE HOOD, DUCT, AND SUPPRESSION
 SYSTEM.
  
 10) TEN INCH TREADS APPEAR TO BE PRESENT
 ON THE STAGE. TEN INCH TREADS DO NOT
 MEET CODE REQUIREMENTS.
  
 11) BUILDING ADDRESS REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910