Plan Review Notes
Plan Review Notes For Permit 03031228
Permit Number 03031228
Review Stop E
Sequence Number 3
Notes
Date Text
2003-07-28 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SEE NOTES FROM TWO REVIEW
 -S. PLEASE CORRELATE RISER DIAGRAMS.
 MP IS STILL SHOWN ON RISER AS "800A MAIN
 S".
 PLANS NOW SHOW A MAIN DISCONNECT OUTSIDE
 AND NOT ENOUGH INFORMATION FOR THIS MAIN
 PLEASE SHOW SIZING ETC.
 PANEL MP MAY BE A MCB PANEL, AS LONG
 AS THERE IS NO MORETHAN 8' OF UNPROTECT
 -ED CONDUCTORS INSIDE THE BLDG.
 210-70 OF LOCAL AMENDMENTS. ALL OTHER
 INFORMATION PER, 215-5,240-3, 230-2,
 230-71,,,
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SEE ATTACHED LETTER PER FS 553.80
 (2)(B). PLEASE NOTE, THIS NOTE AND
 LETTER WAS ATTACHED TO LAST SET OF NOTES
 AS A NOTICE TO DESIGN PROFESSIONALS.
 PLEASE NOTE, A 4X FEE FOR PLAN REVIEW
 PORTION OF PERMIT FEES WILL BE ACCESSED
 AND DUE UPON NEXT SUBMITTAL.
 PLEASE ALSO SEE COMMENTS FROM FIRE,
 BLDG, AND PLUMB FOR REPEAT COMMENTS.
 BZ # 228657 $11,100.00
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]